Experimental evaluation of a R134a/CO2 cascade refrigeration plant

  • Sanz Kock, Carlos
  • Llopis, Rodrigo
  • Sánchez, Daniel
  • Cabello, Ramón
  • Torrella Alcaraz, Enrique
We present the experimental evaluation of a R134a/CO2 cascade refrigeration plant designed for low evaporation temperature in commercial refrigeration applications. The test bench incorporates two single-stage vapour compression cycles driven by semi hermetic compressors coupled thermally through two brazed plate cascade heat exchangers working in parallel and controlled by electronic expansion valves. The experimental evaluation (45 steady-states) covers evaporating temperatures from 40 to 30 C and condensing from 30 to 50 C. In each steady-state, we conducted a sweep of the condensing temperature of the low temperature cycle with speed variation of the high temperature compressor. Here, the energy performance of the plant is analysed, focussing on the compressors' performance, temperature difference in the cascade heat exchanger, cooling capacity, COP and compressors discharge temperatures., The authors gratefully acknowledge Jaume I University of Spain, who financed the present study through the research project P1.B2013-10.
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publication Artículo científico (JournalArticle)

Experimental comparison between R152a and R134a working in a refrigeration facility equipped with a hermetic compressor

  • Cabello, R.
  • Sanchez, D.
  • Llopis Doménech, Rodrigo
  • Armendáriz Araúzo, Luis Miguel
  • Torrella Alcaraz, Enrique
[EN] The EU Regulation 517/2014 has recently been approved in a further attempt to curb the effects of GlobalWarming. As a consequence, the refrigeration sector is moving towards refrigerants with a low GlobalWarming Potential (GWP100) in accordance with the limit fixed by these regulations (150). In this regard, the old refrigerant R152a attracts renewed interest due to its low GWP (138) and its similarity to R134a. The present work shows the results of using R152a in a vapour compression plant equipped with a hermetic compressor and an IHX designed for R134a. The refrigerant was replaced by a conventional drop-in process in order to carry out an energy comparison. The results have revealed an improvement in the COP with R152a up to 13% despite a reduction in the cooling capacity of about 10%. During the test campaign, R134a hermetic compressors have been shown to be capable of operating with R152a., The authors acknowledge Jaume I University of Spain, who financed partially the present study through the research project P1.B2013-10.
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publication Artículo científico (JournalArticle)

Energy and environmental comparison of two-stage solutions for commercial refrigeration at low temperature: Fluids and systems

  • Llopis, Rodrigo
  • Sánchez, Daniel
  • Sanz Kock, Carlos
  • Cabello, Ramón
  • Torrella Alcaraz, Enrique
International agreements will restrict in the near future the use of high-GWP refrigerants in Europe. These restrictions will favour the implantation of refrigeration systems with low-GWP fluids, especially in applications with high leakage rate. To clarify possible solutions that accomplish the forthcoming F-Gas Regulation, we present simplified models of five two-stage vapour compression refrigeration systems and evaluate them with low-GWP refrigerants (HFC, HFO and naturals). We analyse the energy performance over a wide range of evaporating and environment temperatures and present the TEWI analysis under a same scenario, typical of a centralized commercial refrigeration application. We conclude that, for high-GWP refrigerants, direct emissions have greater weight in TEWI than the indirect ones, so future solutions might be based on low-GWP fluids, in some cases with risk of toxicity or flammability. We observe the indirect two-stage systems (cascades) with CO2 as low temperature fluid are promising solutions, especially for warm regions., The authors gratefully acknowledge Jaume I University of Spain, who financed the present study through the research project P1.B2013-10.
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publication Artículo científico (JournalArticle)

Experimental evaluation of an internal heat exchanger in a CO2 subcritical refrigeration cycle with gas-cooler

  • Llopis Doménech, Rodrigo
  • SANZ Kock, Carlos
  • Cabello, Ramon
  • Sanchez, Daniel
  • Torrella Alcaraz, Enrique
We present the experimental evaluation of an internal heat exchanger or suction-line/liquid-line heat exchanger in a CO2 subcritical refrigeration plant with gas-cooler. The plant, driven by a 1.5 kW CO2 semi hermetic compressor, uses brazed plate heat exchangers as condenser, evaporator and internal heat exchanger, an air finned tube gas-cooler and an electronic expansion valves. The evaluation (77 steadystates) covers evaporating temperatures from 40 to 25 C and condensing temperatures from 15 to 0 C, always at the nominal speed of the compressor. Here, the effect of the internal heat exchanger on the main energy parameters is analysed, i.e., cooling capacity, COP and heat rejection at gas-cooler and condenser. Also, the effect of the internal heat exchanger in a cascade cycle is analysed theoretically. It has been concluded that the internal heat exchanger does not improve the performance of the subcritical cycle, but it could improve the energy performance if it is used inside a cascade refrigeration system., The authors gratefully acknowledge Jaume I University of Spain, who financed the present study through the research project P1.B2013-10.
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publication Artículo científico (JournalArticle)

Energy improvements of CO2 transcritical refrigeration cycles using dedicated mechanical subcooling

  • Llopis Doménech, Rodrigo
  • Cabello, Ramon
  • Sanchez, Daniel
  • Torrella Alcaraz, Enrique
[EN] In this work the possibilities of enhancing the energy performance of CO2 transcritical refrigeration systems using a dedicated mechanical subcooling cycle are analysed theoretically. Using simplified models of the cycles, the modification of the optimum operating conditions of the CO2 transcritical cycle by the use of the mechanical subcooling are analysed and discussed. Next, for the optimum conditions, the possibilities of improving the energy performance of the transcritical cycle with the mechanical subcooling are evaluated for three evaporating levels (5, 5 and 30 C) for environment temperatures from 20 to 35 C using propane as refrigerant for the subcooling cycle. It has been observed that the cycle combination will allow increasing the COP up to a maximum of 20% and the cooling capacity up to a maximum of 28.8%, being both increments higher at high evaporating levels. Furthermore, the results indicate that this cycle is more convenient for environment temperatures above 25 C. Finally, the results using different refrigerants for the mechanical subcooling cycle are presented, where no important differences are observed., The authors gratefully acknowledge Jaume I University of Spain, who financed the present study through the research project P1.B2013-10.