TECNALIA Publications
Publicación Artículo científico (JournalArticle)

Data-driven assessment for the supervision of District Heating Networks

  • Eguiarte, Olaia
  • Garrido-Marijuan, Antonio
  • Garay-Martinez, Roberto
  • Raud, Margus
  • Hagu, Indrek
There is an ongoing trend towards temperature reduction in District Heating Networks, allowing for the reduction of distribution heat loss and enabling the integration of low exergy heat production systems. There is a clear scientific consensus on the improved sustainability of such systems. However, there is not sufficient knowledge on how to deliver a successful transition to a low temperature District Heating system, while ensuring the operational levels of the existing system. This paper presents the experience on the progressive temperature reduction of a district heating subnetwork over the 2018–2021 period in Tartu, Estonia. Data from heat meters is extensively used to assess the capacity of substations and network branches to deliver the required heat and quality levels. Faulty substations are identified for targeted assessment and improvement works. Several substations have been identified as missing some of the performance criteria. This has led to further analysis, closer supervision and interventions in the operational conditions of the network. This is an ongoing process, expected to remain in the established procedures of the DH network operator. At the end of the process, a temperature reduction of 7 ºC has shown an improvement of 4.8% in network heat loss.
TECNALIA Publications
Publicación Artículo científico (JournalArticle)

Energy & economic assessment of façade-integrated solar thermal systems combined with ultra-low temperature district-heating

  • Lumbreras, Mikel
  • Garay, Roberto
This paper conducts an energy and economic assessment of District Heating (DH) integrated Solar Thermal (ST) systems. An implementation with building-integrated ST collectors coupled to a Low Temperature District Heating (LTDH) system is studied, with special focus on unglazed collectors. ST heat is exploited in the building through direct use, while excess heat is delivered to the network. A novel control strategy for heat flows in the system is proposed. A meta-analysis of several DH configurations, interconnection schemes and installed ST capacity is performed in three different climates: Sevilla (Spain), Bordeaux (France) & Copenhagen (Denmark). Heat loads corresponding to buildings with various insulation levels and domestic hot water loads are assessed in hourly simulations. The proposed interconnection concept provides a variety of connection modes to the DH network, allowing up to a 50% increase in the provision of solar heat compared to an isolated ST system. Positive Return of Investment (ROI) for such a setup is achieved in 22% of the studied cases. The DH network is found to be a suitable heat sink in up to 25% of the buildings with ST systems installed.
TECNALIA Publications
Publicación Artículo científico (JournalArticle)

RELaTED Project: New Developments on Ultra-Low Temperature District Heating Networks

  • Marijuan, Antonio Garrido
  • Garay, Roberto
  • Lumbreras, Mikel
  • Sánchez, Víctor
  • Macias, Olga
  • Rozas, Juan Perez Sainz De
District heating networks deliver around 13% of the heating energy in the EU, being considered as a key element of the progressive decarbonization of Europe. The H2020 REnewable Low TEmperature District project (RELaTED) seeks to contribute to the energy decarbonization of these infrastructures through the development and demonstration of the following concepts: reduction in network temperature down to 50 °C, integration of renewable energies and waste heat sources with a novel substation concept, and improvement on building-integrated solar thermal systems. The coupling of renewable thermal sources with ultra-low temperature district heating (DH) allows for a bidirectional energy flow, using the DH as both thermal storage in periods of production surplus and a back-up heating source during consumption peaks. The ultra-low temperature enables the integration of a wide range of energy sources such as waste heat from industry. Furthermore, RELaTED also develops concepts concerning district heating-connected reversible heat pump systems that allow to reach adequate thermal levels for domestic hot water as well as the use of the network for district cooling with high performance. These developments will be demonstrated in four locations: Estonia, Serbia, Denmark, and Spain.
TECNALIA Publications
Publicación Artículo científico (JournalArticle)

Data driven model for heat load prediction in buildings connected to District Heating by using smart heat meters

  • Lumbreras, Mikel
  • Garay-Martinez, Roberto
  • Arregi, Beñat
  • Martin-Escudero, Koldobika
  • Diarce, Gonzalo
  • Raud, Margus
  • Hagu, Indrek
An accurate characterization and prediction of heat loads in buildings connected to a District Heating (DH) network is crucial for the effective operation of these systems. The high variability of the heat production process of DH networks with low supply temperatures and derived from the incorporation of different heat sources increases the need for heat demand prediction models. This paper presents a novel data-driven model for the characterization and prediction of heating demand in buildings connected to a DH network. This model is built on the so-called Q-algorithm and fed with real data from 42 smart energy meters located in 42 buildings connected to the DH in Tartu (Estonia). These meters deliver heat consumption data with a 1-h frequency. Heat load profiles are analysed, and a model based on supervised clustering methods in combination with multiple variable regression is proposed. The model makes use of four climatic variables, including outdoor ambient temperature, global solar radiation and wind speed and direction, combined with time factors and data from smart meters. The model is designed for deployment over large sets of the building stock, and thus aims to forecast heat load regardless of the construction characteristics or final use of the building. The low computational cost required by this algorithm enables its integration into machines with no special requirements due to the equations governing the model. The data-driven model is evaluated both statistically and from an engineering or energetic point of view. R2 values from 0.70 to 0.99 are obtained for daily data resolution and R2 values up to 0.95 for hourly data resolution. Hourly results are very promising for more than 90% of the buildings under study.
TECNALIA Publications
Publicación Artículo científico (JournalArticle)

Unglazed Solar Thermal Systems for Building Integration, coupled with District Heating Systems. Conceptual Definition, Cost and Performance Assessment

  • Lumbreras, Mikel
  • Garay, Roberto
  • Martin, Koldobika
In this paper, the energy performance of a Solar Thermal (ST) façade system is studied for its connection to a District Heating System. This concept allows for the direct use of ST heat in the building, while taking profit from the network for delivery/selling of excess heat and purchase of heat during periods of underproduction. The use of Unglazed Collectors for low-intrusive architectural interaction in façades is discussed. Studies are carried out on the heat production of the system and its capacity to cope with local demands. Economic studies are carried out in order to balance the investment and operational costs/profits of the system.
TECNALIA Publications
Publicación Artículo científico (JournalArticle)

Lessons Learnt from Substation Inspection on Low Temperature District Heating Networks

  • Garrido-Marijuan, Antonio
  • Eguiarte, Olaia
  • Garay-Martinez, Roberto
  • Raud, Margus
  • Hagu, Indrek
District heating networks are considered to be a key element for the decarbonization of Europe. The RELaTED project seeks to contribute to the decarbonization of these infrastructures with the demonstration of low temperature district heating networks. One of the demonstration sites consists of more than 50 substations within a subsection of a larger network in the city of Tartu (Estonia), where the temperature was lowered by 10 ◦C. To ensure the benefits of this new generation district heating network and the fulfillment of comfort requirements, data have been monitored and analyzed at the substation level in an automatic way to facilitate the inspection of every user.
Addi. Archivo Digital para la Docencia y la Investigación
Publicación Artículo científico (JournalArticle)

Unsupervised recognition and prediction of daily patterns in heating loads in buildings

  • Lumbreras Mugaguren, Mikel
  • Diarce Belloso, Gonzalo
  • Martín Escudero, Koldobika
  • Garay Martínez, R.
  • Arregui, Beñat
This paper presents a multistep methodology combining unsupervised and supervised learning techniques for the identification of the daily heating energy consumption patterns in buildings. The relevant number of typical profiles is obtained through unsupervised clustering processes. Then Classification and Regression Trees are used to predict the profile type corresponding to external variables, including calendar and climatic variables, from any given day. The methodology is tested with a variety of datasets for three different buildings with different uses connected to the district heating network in Tartu (Estonia). The three buildings under analysis present different energy behaviors (residential, kindergarten and commercial buildings). The paper shows that unsupervised clustering is effective for pattern recognition since the results from the classification and regression trees match the results from the unsupervised clustering. Three main patterns have been identified in each building, seasonality and daily mean temperature being the variables that have the greatest effect. The results concluded that the best classification accuracy is obtained with a small number of clusters with a classification accuracy from 0.7 to 0.85, approximately., The authors would like to thank GREN Eesti [44] for providing data from the substations for academic purposes. The authors would like to acknowledge the Spanish Ministry of Science and Innovation (MICINN) for funding through the Sweet-TES research project (RTI2018-099557-B-C22). This project has received funding from the European Union's Horizon 2020 research and innovation programme under grant agreement No 768567.
Addi. Archivo Digital para la Docencia y la Investigación
Publicación Artículo científico (JournalArticle)

Data driven model for heat load prediction in buildings connected to District Heating by using smart heat meters

  • Lumbreras Mugaguren, Mikel
  • Garay Martínez, R.
  • Arregui, Beñat
  • Martín Escudero, Koldobika
  • Diarce Belloso, Gonzalo
  • Raud, Margus
  • Hagu, Indrek
[EN] An accurate characterization and prediction of heat loads in buildings connected to a District Heating (DH) network is crucial for the effective operation of these systems. The high variability of the heat production process of DH networks with low supply temperatures and derived from the incorporation of different heat sources increases the need for heat demand prediction models. This paper presents a novel data-driven model for the characterization and prediction of heating demand in buildings connected to a DH network. This model is built on the so-called Q-algorithm and fed with real data from 42 smart energy meters located in 42 buildings connected to the DH in Tartu (Estonia). These meters deliver heat consumption data with a 1-h frequency. Heat load profiles are analysed, and a model based on supervised clustering methods in combination with multiple variable regression is proposed. The model makes use of four climatic variables, including outdoor ambient temperature, global solar radiation and wind speed and direction, combined with time factors and data from smart meters. The model is designed for deployment over large sets of the building stock, and thus aims to forecast heat load regardless of the construction characteristics or final use of the building. The low computational cost required by this algorithm enables its integration into machines with no special requirements due to the equations governing the model. The data-driven model is evaluated both statistically and from an engineering or energetic point of view. R-2 values from 0.70 to 0.99 are obtained for daily data resolution and R-2 values up to 0.95 for hourly data resolution. Hourly results are very promising for more than 90% of the buildings under study. (, This study has been carried out in the context of RELaTED project. This project has received funding from the European Union's Horizon 2020 research and innovation programme under grant agreement No 768567. This publication reflects only the authors' views and neither the Agency nor the Commission are responsible for any use that may be made of the information contained therein.