Skip to main content

CONTROL COOPERATIVO PARA LA GESTION OPTIMA DE LA ENERGIA EN MICRORREDES ELECTRICAS INTELIGENTES

ENE2012-37667-C02-02

•
Funding agency name Ministerio de Economía y Competitividad
Funding agency acronym MINECO
Program Programa Nacional de Proyectos de Investigación Fundamental
Subprogram Subprograma de Proyectos de Investigación Fundamental no Orientada
Call Proyectos I+D
Call year 2012
State Plan 2008-2011 Plan Nacional de Investigación Científica, Desarrollo e Innovación Tecnológica
Management unit Secretaría de Estado de Investigación, Desarrollo e Innovación
Beneficiary centre UNIVERSITAT POLITECNICA DE CATALUNYA

Resultados relacionados

Resultados totales (Incluyendo duplicados): 1
Encontrada(s) 1 página(s)

Recercat. Dipósit de la Recerca de Catalunya
Publication Contribución de congreso (ConferenceOutput)

Performance analysis of frequency restoration for parallel voltage source inverters connected with a realistic communication channel

  • Martí Colom, Pau
  • Velasco García, Manel
  • Martín Rull, Enric Xavier
  • Castilla Fernández, Miguel
  • Miret Tomàs, Jaume
  • Torres Martínez, Javier
A topic of interest within the microgrid (MG) community is to achieve accurate sharing of active and reactive power among voltage source inverters (VSI) working in parallel while keeping the voltage frequency and amplitude stable, and close to a given reference. This problem has been mainly solved by the so-called frequency and voltage droop controllers that are local control loops implemented in each VSI. However, since they introduce a frequency and amplitude deviation, a secondary integral-like control loop using a communication system is usually deployed to enable each VSI to cancel the deviations. This paper evaluates two secondary control implementations of the frequency restoration with respect to properties of the communication system. Networked control applications are subject to known problems that are inherent to the use of a communication system such as message losses or varying sampling/transmission intervals, to name a few. The performance analysis reveals that control policies should be designed accounting also for the properties of the communication system. Otherwise, unexpected results violating the control specifications may appear., Peer Reviewed, Postprint (published version)