Publicación Artículo científico (JournalArticle)

On the Influence of Operational and Control Parameters in Thermal Response Testing of Borehole Heat Exchangers

  • Badenes Badenes, Borja|||0000-0002-3469-9265
  • Mateo Pla, Miguel Ángel|||0000-0002-8059-6996
  • Lemus Zúñiga, Lenin Guillermo|||0000-0002-6361-6019
  • Saiz Mauleón, María Begoña|||0000-0002-8650-0916
  • Urchueguía Schölzel, Javier Fermín|||0000-0002-3054-3431
[EN] Thermal response test (TRT) is a common procedure for characterization of ground and borehole thermal properties needed for the design of a shallow geothermal heat pump system. In order to investigate and to develop more accurate and robust procedures for TRT control, modelling, and evaluation in semi-permeable soils with large water content, a pilot borehole heat exchanger was built in the main campus of the Universitat Politècnica de València. The present work shows the results of the experiments performed at the site, analysing the improvements that have been introduced both in the control of the heat injected during TRTs and in the methods to infer the ground thermal parameter. Three models are compared: two based on the infinite-line source theory and one based on the finite-line source scheme. The models were tested under two possible configurations of the equipment, i.e., with and without strict control of injected heat. Our results show the importance of heat injection control for a robust parameter assessment and the existence of additional heat transfer processes that the used models cannot completely characterize and that are related to the presence of significant groundwater flow at the site. In addition, our experience with the current installation and the knowledge about its strengths and weaknesses have allowed us to design a new and more complete test-site to help in the analysis and validation of new ground heat exchanger geometries., This work has received funding from the European Union’s Horizon 2020 Research and Innovation program under grant agreement Nos. (657982) and (727583).
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publicación Artículo científico (JournalArticle)

Adapted composite two-region line source methods for evaluation of borehole heat exchangers with advanced materials

  • Urchueguía Schölzel, Javier Fermín|||0000-0002-3054-3431
  • Badenes Badenes, Borja|||0000-0002-3469-9265
  • Javadi, Hossein|||0000-0002-2059-7145
  • Mateo Pla, Miguel Ángel|||0000-0002-8059-6996
  • Armengot-Carbó, B.|||0000-0001-7424-2975
[EN] The results of a large number of Thermal Response Tests (TRTs) performed on four different borehole heat exchangers (BHEs) were analyzed to explore the effect of the novel grouting and plastic pipe materials developed in a previous project on their thermal performance. For this purpose, two versions of the composite two-region line source approach have been adapted for its use for evaluating BHEs in practical situations, allowing us to obtain more comprehensive and consistent information on key thermal parameters of ground and fillers. We develop a scheme that combines the composite two-region model with unsteady TRT injection data to avoid some shortcomings that have appeared in previous implementations of this approach. Our new method enables us to obtain parameters otherwise difficult to obtain, such as the diffusivities, heat capacities, and conductivities of ground and grout. In comparison with standard line source based analysis, it allows to improve and enrich TRT execution, with a reduction in the test time required, lower uncertainties of the parameters obtained, and a deeper understanding of the thermal properties of the grout, ground, and borehole heat exchanger as all estimates are correlated to actual physical, mensurable soil and ground properties, which allows independent critical revision and check against alternative estimation methods.
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publicación Artículo científico (JournalArticle)

A European Database of Building Energy Profiles to Support the Design of Ground Source Heat Pumps

  • Carnieletto, Laura
  • Belliardi, Marco
  • Bernardi, Adriana
  • Graci, Samantha
  • Emmi, Giuseppe
  • Zarrella, Angelo
  • Di Bella, Antonino
  • Dalla Santa, Giorgia
  • Galgaro, Antonio
  • Mezzasalma, Giulia
  • De Carli, Michele
  • Badenes Badenes, Borja|||0000-0002-3469-9265
  • Urchueguía Schölzel, Javier Fermín|||0000-0002-3054-3431
[EN] The design of ground source heat pumps is a fundamental step to ensure the high energy efficiency of heat pump systems throughout their operating years. To enhance the diffusion of ground source heat pump systems, two different tools are developed in the H2020 research project named, Cheap GSHPs: A design tool and a decision support system. In both cases, the energy demand of the buildings may not be calculated by the user. The main input data, to evaluate the size of the borehole heat exchangers, is the building energy demand. This paper presents a methodology to correlate energy demand, building typologies, and climatic conditions for different types of residential buildings. Rather than envelope properties, three insulation levels have been considered in different climatic conditions to set up a database of energy profiles. Analyzing European climatic test reference years, 23 locations have been considered. For each location, the overall energy and the mean hourly monthly energy profiles for heating and cooling have been calculated. Pre-calculated profiles are needed to size generation systems and, in particular, ground source heat pumps. For this reason, correlations based on the degree days for heating and cooling demand have been found in order to generalize the results for different buildings. These correlations depend on the Koppen-Geiger climate scale., This work received funding from the European Union's Horizon 2020 research and innovation program under grant agreement No. 657982.
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publicación Artículo científico (JournalArticle)

A Case Study of Thermal Evolution in the Vicinity of Geothermal Probes Following a Distributed TRT Method

  • Schwarz, Hans
  • Wagner, Jan
  • Cuevas, José Manuel
  • Bertermann, David
  • Badenes Badenes, Borja|||0000-0002-3469-9265
  • Urchueguía Schölzel, Javier Fermín|||0000-0002-3054-3431
[EN] To meet the stated climate change targets and to ensure the capability of meeting the current and future energy demands, there is an urgent need to develop renewable energy sources, such as geothermal systems. If geothermal systems are to be cost-efficient and are to enjoy public confidence, it is essential that they are designed and installed in accordance with the prevailing site-specific conditions. A thorough understanding of the thermal behaviour of the surrounding ground is, therefore, critical. In this work, we investigated temperature and its evolution in the vicinity of a shallow geothermal helix-shaped borehole heat exchanger (BHE). To measure the temperature close to the actual geothermal system, an additional U-tube probe was installed at the edge of the same borehole. A thermal load was then applied to the BHE, and the temperature was detected in the nearby U-tube. The temperature measurements were made with a GEOSniff monitoring device. To understand these localised temperature measurements in the context of the Valencia test site, ERT measurements were also performed. The GEOSniff device permits measurements to be made with very high depth resolution, which allows the thermal properties of the surrounding ground to be derived precisely, thus, enabling the identification of the different textural domains., This research work has been supported financially by the European Cheap-GSHPs Project (funded by the European Union's Horizon 2020 research and innovation program under grant agreement No 657982) and by the European GEO4CIVHIC Project (funded by the European Union's Horizon 2020 research and innovation program under grant agreement No 792355).
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publicación Artículo científico (JournalArticle)

How Reliable Are Standard Thermal Response Tests? An Assessment Based on Long-TermThermal Response Tests Under Different Operational Conditions

  • Urchueguía Schölzel, Javier Fermín|||0000-0002-3054-3431
  • Lemus Zúñiga, Lenin Guillermo|||0000-0002-6361-6019
  • Oliver Villanueva, José Vicente|||0000-0003-2842-7834
  • Badenes Badenes, Borja|||0000-0002-3469-9265
  • Mateo Pla, Miguel Ángel|||0000-0002-8059-6996
  • Cuevas-Castell, José Manuel
[EN] In this contribution, we analyze the results of a number of thermal response test (TRT) experiments performed during several years at the same location at our university campus in Valencia (Spain), a permeable saturated soil area with possible groundwater flow conditions. A combination of different heat injection rates, TRT operation times of up to 32 days, and various methods for parameter estimation of ground thermal properties have been applied to study their influence on the result and accuracy of TRTs. Our main objective has been to experimentally quantify the influence of groundwater flow heat advection using moving infinite and finite line-source theories, as well as to analyze the influence of factors such as test duration, sensor accuracy, and external thermal influences. We have shown that the traditionally used infinite and finite line-source models, as well as the moving line-source models, can accurately represent experimental temperature evolution, but that there are many caveats regarding the significance parameters extracted and its reproducibility and stability. These features can be improved if data from the first test days are disregarded for the analysis, obtaining a much faster convergence to the definitive soil parameter estimates, including the effective Peclet number that represents groundwater flow in our particular case., This research was funded by the European Union's Horizon 2020 Research and Innovation program under grant agreement No [657982] and [727583].