RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publicación Artículo científico (JournalArticle)

Improved water to water heat pump design for low-temperature waste heat recovery based on subcooling control, Conception d&apos, une pompe à chaleur eau-eau optimisée pour la récupération de chaleur perdue à basse température basée sur la régulation du sous-refroidissement

  • Hervas-Blasco, Estefania
  • Corberán, José M.
  • Navarro-Peris, Emilio|||0000-0002-0608-2129
  • Barceló Ruescas, Francisco|||0000-0002-0577-2662
[EN] Traditional heat pumps designs have been optimized for heating applications based on small secondary temperature lifts (around 5K); however, in applications with other characteristic temperature lifts, different design criteria could be required. For instance, transcritical cycles have demonstrated to have a high efficiency for domestic hot water production with high water temperature lifts. This work presents the experimental results of a new water-to-water heat pump composed by the basic heat pump components (condenser, compressor, evaporator, expansion valve and liquid reliever) able to adapt its performance depending on the required water temperature lift. Domestic hot water production from grey water waste heat recovery has been chosen as experimental application to test this heat pump. Results show COP values up to 5.5 at the design condition (20-15 degrees C at the inlet-outlet of the evaporator and 10-60 degrees C at the inlet-outlet of the condenser) and an optimal degree of subcooling of 47 K. (C) 2019 Elsevier Ltd and IIR. All rights reserved., Part of the results of this study were developed in the mainframe of the FP7 European project 'Next Generation of Heat Pumps working with Natural fluids' (NxtHPG). Part of the work presented was carried out by Estefania Hervas Blasco with the financial support of a PhD scholarship from the Spanish government SFPI1500 x 074478XV0. The authors would like also to acknowledge the Spanish 'MINISTERIO DE ECONOMIA Y COMPETITIVIDAD', through the project "MAXIMIZACION DE LA EFICIENCIA Y MINIMIZACION DEL IMPACTO AMBIENTAL DE BOMBAS DE CALOR PARA LA DESCARBONIZACION DE LA CALEFACCION/ACS EN LOS EDIFICIOS DE CONSUMO CASI NULO"with the reference ENE2017-83665-C2-1-P for the given support.
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publicación Artículo científico (JournalArticle)

Hot sanitary water production with CO2 heat pumps: Effect of control strategy on system performance and stratification inside the storage tank

  • Tammaro, Marcello
  • Mauro, A. W.
  • Corberán Salvador, José Miguel
  • Mastrullo, R.
  • Montagud- Montalvá, Carla|||0000-0002-7118-6119
[EN] In this work three different control strategies for the production of sanitary hot water by means of an electric heat pump working with CO2 are investigated. The heat pump is a prototype, here modelled in the vapour-compression software package IMST-ART. By simulating this model, the performance of the heat pump is correlated to the boundary conditions and is scaled to different sizes, namely 1, 1.5, and 2 times larger than the reference system. After having chosen an application for which the load profile of sanitary hot water during the year is known, these heat pumps are simulated in a TRNSYS16 model where the production of sanitary hot water and the consumption are buffered by the presence of a tank. Key parameter in guaranteeing comfort and good performance of the system is the stratification inside the storage tank. The size of the tank necessary to keep a certain level of comfort at the user is then determined through a parametric analysis for each size of the heat pump. The energetic performance is also evaluated for each system in terms of seasonal performance factor. Then, the results obtained are compared with a different system where the heat pump is equipped with an inverter and the circulation pump follows a different control logic. The size of the tank and the seasonal performance factor are therefore determined in this case too. Moreover, a night&day control logic is compared to these first two options to have a baseline of comparison in terms of volume of storage needed to guarantee a same level of comfort and performance. To provide information also on the running costs, a parametric analysis was run varying the type of control, the heat pump and the tank sizes for different load profiles. The results show that the size of the heat pump has a significant effect on the comfort of the user, which usually leads to oversizing of the storage tank when the load profile is unknown. With regard to this, the results obtained for the alternative control system show a 20% reduction of the volume of the tank, given a certain level of comfort, and is therefore useful to reduce the size of the storage tank., The study related to thiswork has been partially supported by the FP7 European project ‘Next Generation of Heat Pumpsworkingwith Natural fluids’ (NxtHPG) Grant agreement no: 307169. The work of M. Tammaro on electric heat pumps is financially supported by Universita degli Studi di Napoli Federico II throughthe FP7 European project 'Next Generation of Heat Pumps working with Natural fluids' (NxtHPG).
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publicación Artículo científico (JournalArticle)

Analysis and optimization of different two-stage transcritical carbon dioxide cycles for heating applications

  • Pitarch Mocholí, Miguel
  • Corberán Salvador, José Miguel
  • Navarro-Peris, Emilio|||0000-0002-0608-2129
  • Gonzálvez-Maciá, José|||0000-0001-9422-7756
[EN] Increased interest in the environmental impact of refrigeration technology is leading toward design solutions aimed at improving the energy efficiency and use of eco-friendly refrigerants with low GWP. The aim of this paper is to theoretically analyse R744 air to water heat pump cycles for heating applications up to 80 °C. This work studies the following cycle configurations: two-stage with injection (with and without intermediated cooling between compressors) and a single-stage circuit coupled with an auxiliary circuit. Internal heat transfer among the different streams of refrigerant is included, and the cycles have been optimized with regards to COP in terms of the intermediate conditions and gas cooler pressure. Finally, these cycles have been compared and analysed among each other and with a subcritical injection cycle working with R134a and a single-stage R744 cycle. The improved cycle with R744 can represent a global improvement of 15% in terms of COP., This work has been developed in the 7 framework program of the European Union by the project Next Generation of Heat Pump Technologies (NEXTGHP) grant agreement 307169. The authors give thanks for the given support. Part of the work presented was carried by Miquel Pitarch-Mocholi with the financial support of the Phd scholarship from the Universitat Politecnica de Valencia.
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publicación Artículo científico (JournalArticle)

Seasonal performance assessment of sanitary hot water production systems using propane and CO2 heat pumps

  • Tammaro, M.
  • Montagud, C.
  • Corberán, J.M.
  • Mauro, A.W.
  • Mastrullo, R.
[EN] This paper presents an experimental analysis and performance evaluation of a ground source heat pumpsystem providing heating/cooling to an office building, located at the Universitat Politècnica de Valènciain Spain. The experimental data and a detailed description of the analysis tool used were presented ina previous paper for the first six operational years. This paper provides the adaptation of such analysistool to the new configuration (heat pump with two compressors working in tandem), and provides anupdated complete reference data sets over more than eleven years which can be used by researchers formodel validation purposes., The work of M. Tammaro on electric heat pumps is supported by the Next Heat Pump Generation project (funded by the European Commission in the 7th Framework Programme, grant number 307169 - European Heat Pump Association, 2013), which is gratefully acknowledged.
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publicación Artículo científico (JournalArticle)

Evaluation of optimal subcooling in subcritical heat pump systems

  • Pitarch, Miquel
  • Hervas-Blasco, Estefanía
  • Corberán, José M.
  • Navarro-Peris, Emilio|||0000-0002-0608-2129
  • Gonzálvez-Maciá, José|||0000-0001-9422-7756
[EN] The performance of a transcritical cycle is highly dependent on the rejection pressure. The optimal rejection pressure depends mainly on the inlet and outlet temperatures at the heat sink (secondary fluid). For the subcritical cycles, recent studies have demonstrated that the performance of these systems depends significantly on the degree of subcooling and its optimal value varies depending on the application. This paper presents a general methodology to calculate the optimal subcooling depending on the boundary conditions. The refrigerants R290, R134a, R1234yf and R32 are analyzed. Exergy analysis is used in order to see the subcooling effect at condenser and expansion valve independently. The optimal subcooling strongly depends on the temperature lift at the secondary fluid, and it is found when two pinch points are given in the condenser, one at the condenser outlet and another one inside the condenser (at the refrigerant dew point)., Part of the results of this study were developed in the mainframe of the FP7 European project "Next Generation of Heat Pumps working with Natural fluids" (NxtHPG). Part of the work presented was carried by Miguel Pitarch-Mocholi with the financial support of the PhD scholarship from the Universitat Politecnica de Valencia. The authors would like to acknowledge the Spanish "MINISTERIO DE ECONOMIA Y COMPETITIVIDAD", through the project ref-ENE2014-53311-C2-1-P-AR "Aprovechamiento del calor residual a baja temperatura mediante bombas de calor para la produccion de agua caliente" for the given support.
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publicación Artículo científico (JournalArticle)

Exergy analysis on a heat pump working between a heat sink and a heat source of finite heat capacity rate

  • Pitarch, Miguel
  • Hervás-Blasco, Estefanía
  • Corberán, José M.
  • Navarro-Peris, Emilio|||0000-0002-0608-2129
[EN] The optimum performance of a pure subcritical refrigeration cycle depends significantly on the temperature lift of the heat source and sink. Therefore, the maximization of the system efficiency has to be linked to them. This paper shows an exergy analysis of each heat pump component (condenser, evaporator, expansion valve and compressor) considering that the heat source and sink are not at constant temperature. The performed study shows the components with more possibilities for improvement. Based on this analysis, the optimization of cycle parameters like subcooling and superheat as a function of the external conditions have been done. In addition, this work has demonstrated that the components having a higher influence in the system irreversibility's depends significantly on the temperature lift of the secondary fluids. Finally, the obtained results show potentials improvements of the efficiency up to 23% if the system is able to operate in the optimal subcooling and superheat., Part of the results of this study were developed in the mainframe of the FP7 European project 'Next Generation of Heat Pumps workingwith natural fluids' (NxtHPG). Part of the work presented was carried by Miquel Pitarch with the financial support of a PhD scholarship from the Universitat Politecnica de Valencia. Part of the work presented was carried by Estefania Hervas-Blasco with the financial support of a Ph.D. scholarship from the Spanish government SFPI1500X074478XV. The authors would like also to acknowledge the Spanish 'MINISTERIO DE ECONOMIA Y COMPETITIVIDAD', through the Project ENE2017-83665-C2-1-P, "Maximizacion de la Eficiencia y Minimizacion del Impacto Ambiental de Bombas de Calor para la descarbonizacion de la calefaccion/ACS en los proximos edificios de consumo energetico casi nulo" for the given support.
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publicación Artículo científico (JournalArticle)

Experimental study of a subcritical heat pump booster for sanitary hot water production using a subcooler in order to enhance the efficiency of the system with a natural refrigerant (R290)

  • Pitarch, M.
  • Corberán, José M.
  • Navarro-Peris, Emilio|||0000-0002-0608-2129
  • Gonzálvez-Maciá, José|||0000-0001-9422-7756
[EN] This paper presents the experimental results obtained from a new heat pump prototype for sanitary hot water production, in the application of heat recovery from water sources like sewage water or condensation loops (typical temperature condition between 10 degrees C and 30 degrees C). The system configuration is able to produce a high degree of subcooling in order to take advantage from the high water temperature glide (typical value for sanitary hot water production is 10 degrees C to 60 degrees C). Subcooling is made by using a separate heat exchanger from the condenser (subcooler). The obtained results have shown a high degree of improvement by making subcooling. COP is 5.61 in nominal conditions, which is about 31% higher than the same cycle working without subcooling (Nominal point: inlet/outlet water temperature at evaporator is 20 degrees C/15 degrees C and the water inlet/outlet temperature in the heat sink is 10 degrees C and 60 degrees C). (C) 2016 Elsevier Ltd and HR. All rights reserved., This work has been developed in the European Union Seventh Framework Programme by the project Next Generation of Heat Pump Technologies (NEXTGHP) grant agreement 307169. The authors give thanks for the given support. Part of the work presented was carried by Miguel Pitarch-Mocholi with the financial support of the Phd scholarship from the Universitat Politecnica de Valencia.
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publicación Artículo científico (JournalArticle)

A propane water-to-water heat pump booster for sanitary hot water production: Seasonal performance analysis of a new solution optimizing COP

  • Tammaro, Marcello
  • Corberán Salvador, José Miguel
  • Mauro, Alfonso William
  • Mastrullo, R.
  • Montagud- Montalvá, Carla|||0000-0002-7118-6119
[EN] Electrical heat pumps for sanitary hot water production achieve a high performance with a good matching of water and refrigerant temperature profiles during the heat rejection stage, as it happens in CO2 systems. This work considers the thermodynamic possibility to adapt the condenser pressure of a propane heat pump to maximize the COP, while producing sanitary hot water up to 60 C from a heat sink equal to 15 or 25 C. The performance of the heat pump is calculated through specific models which, in combination with a TRNSYS model of the whole system, allowed to assess its seasonal performance for a hotel in Strasbourg, also varying the control logic and the size of the storage tank. Results obtained led to the conclusion that, for achieving a high seasonal performance, the control logic of the tank has the largest influence., Part of the results of this study were developed in the mainframe of the FP7 European project ‘Next Generation of Heat Pumps working with Natural fluids’ (NxtHPG). Part of the work presented was carried by M. Tammaro during his visit at the Instituto de Ingenierı´a Energetica, Universitat Politecnica de Val encia and by C. Montagud during her visit at the Department of Industrial Engineering, Federico II University of Naples, with the financial support of the POLIGRID project.
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publicación Artículo científico (JournalArticle)

Evaluation of different heat pump systems for sanitary hot water production using natural refrigerants

  • Pitarch, Miguel
  • Corberán, José M.
  • Navarro-Peris, Emilio|||0000-0002-0608-2129
  • Gonzálvez-Maciá, José|||0000-0001-9422-7756
[EN] Heat pumps that work with a high degree of subcooling in subcritical systems have shown a significant margin of improvement when working with sanitary hot water applications. Recently, two different approaches to overcome the high degree of subcooling have been presented in the literature: with a subcooler (separate from the condenser) and by making all the subcooling in the condenser. In this paper, a comparative evaluation between both alternatives is presented, and the obtained results are compared with a representative solution already available on the market using natural refrigerants for this application. The results of this analysis have shown that in a system with subcooling in the condenser, it is possible to obtain a COP comparable to that of transcritical CO2 heat pump water heaters. Furthermore, the system with subcooling has been demonstrated experimentally as being capable of producing water up to 90ºC and has shown a COP up to 20% higher than some CO2 commercial products (catalogue data reference)., This work has been developed in the Seventh Framework Program of the European Union by the project, Next Generation of Heat Pump Technologies (NEXTGHP), grant agreement 307169. The authors thank the support given. Part of the work presented was carried by Miquel Pitarch-Mocholí with the financial support of a PhD scholarship from the Universitat Politècnica de València. The authors would like also to acknowledge the Spanish ‘MINISTERIO DE ECONOMIA Y COMPETITIVIDAD’, through the project ref-ENE2014-53311-C2-1-P-AR ‘‘Aprovechamiento del calor residual a baja temperatura mediante bombas de calor para la produccion de agua caliente” for the given support