Experimental analysis of R1234yf as a drop-in replacement for R134a in a vapor compression system, Analyse experimentale du R1234yf comme frigorige`ne de remplacement immediat du R134a dans un systeme a` compression de vapeur
[EN] This paper presents an experimental analysis of a vapor compression system using
R1234yf as a drop-in replacement for R134a. In this work, we compare the energy performance
of both refrigerants, R134a and R1234yf, in a monitored vapor compression system
under a wide range of working conditions. So, the experimental tests are carried out
varying the condensing temperature, the evaporating temperature, the superheating degree,
the compressor speed, and the internal heat exchanger use. Comparisons are made
taking refrigerant R134a as baseline, and the results show that the cooling capacity
obtained with R1234yf in a R134a vapor compression system is about 9% lower than that
obtained with R134a in the studied range. Also, when using R1234yf, the system shows
values of COP about 19% lower than those obtained using R134a, being the minor difference
for higher condensing temperatures. Finally, using an internal heat exchanger these differences
in the energy performance are significantly reduced., This study was sponsored by Fundacio Caixa Castello-Bancaixa under the project P11B2010-24 "Aplicacion de nuevos refrigerantes con bajo potencial de efecto invemadero en sistemas de frio comercial y climatizacion".