Pasar al contenido principal

REDES MVDC INTEGRANDO TECNOLOGIAS DE ENERGIAS RENOVABLES, ALMACENAMIENTO DE ENERGIA Y CONVERTIDORES DC/AC DE FUENTE DE IMPEDANCIA

RTI2018-095720-B-C32

•
Nombre agencia financiadora Agencia Estatal de Investigación
Acrónimo agencia financiadora AEI
Programa Programa Estatal de I+D+i Orientado a los Retos de la Sociedad
Convocatoria Proyectos I+D+i Retos de Investigación
Año convocatoria 2018
Plan Estatal 2017-2020 Plan Estatal de Investigación Científica y Técnica y de Innovación
Centro beneficiario UNIVERSIDAD DE CADIZ

Resultados relacionados

Resultados totales (Incluyendo duplicados): 9
Encontrada(s) 1 página(s)

RODIN. Repositorio de Objetos de Docencia e Investigación de la Universidad de Cádiz
Publicación Contribución de congreso (ConferenceOutput)

Decoupled Maximum Constant Boost Control for Quasi-Z-Source Inverter

  • García Vázquez, Carlos Andrés
  • Sánchez Sainz, Higinio
  • González Rivera, Enrique
  • Llorens Iborra, Francisco
  • Fernández Ramírez, Luis Miguel
Maximum Constant Boost Control (MCBC) is one of the most suitable modulation techniques for Z-Source Inverters (ZSI) and quasi-ZSI (qZSI). Nevertheless, it cannot decouple the output voltage control and the fluctuations of the voltage source at the input of the inverter. This work proposes a new method based on this modulation technique that allows decoupling the control of these two variables, input and output voltages of a qZSI. The simulation results show that the Decoupled Maximum Constant Boost Control (DMCBC) has the same features and advantages than the one without decoupling. Voltage gain, stress and harmonic distortion are studied and the results show that the behavior is not modified, except for the reduction of the boost factor., This work was partially supported by the Spanish Ministry of Science, Innovation and Universities (grant number RTI2018-095720-B-C32).
RODIN. Repositorio de Objetos de Docencia e Investigación de la Universidad de Cádiz
Publicación Artículo científico (JournalArticle)

Optimal energy management system using biogeography based optimization for grid-connected MVDC microgrid with photovoltaic, hydrogen system, electric vehicles and Z-source converters

  • De Oliveira-Assis, Lais
  • García Triviño, Pablo
  • Soares-Ramos, Emanuel P. P.
  • Sarrias Mena, Raúl
  • García Vázquez, Carlos Andrés
  • Ugalde-Loo, Carlos Ernesto
  • Fernández Ramírez, Luis Miguel
Currently, the technology associated with charging stations for electric vehicles (EV) needs to be studied and improved to further encourage its implementation. This paper presents a new energy management system (EMS) based on a Biogeography-Based Optimization (BBO) algorithm for a hybrid EV charging station with a configuration that integrates Z-source converters (ZSC) into medium voltage direct current (MVDC) grids. The EMS uses the evolutionary BBO algorithm to optimize a fitness function defining the equivalent hydrogen consumption/generation. The charging station consists of a photovoltaic (PV) system, a local grid connection, two fast charging units and two energy storage systems (ESS), a battery energy storage (BES) and a complete hydrogen system with fuel cell (FC), electrolyzer (LZ) and hydrogen tank. Through the use of the BBO algorithm, the EMS manages the energy flow among the components to keep the power balance in the system, reducing the equivalent hydrogen consumption and optimizing the equivalent hydrogen generation. The EMS and the configuration of the charging station based on ZSCs are the main contributions of the paper. The behaviour of the EMS is demonstrated with three EV connected to the charging station under different conditions of sun irradiance. In addition, the proposed EMS is compared with a simpler EMS for the optimal management of ESS in hybrid configurations. The simulation results show that the proposed EMS achieves a notable improvement in the equivalent hydrogen consumption/generation with respect to the simpler EMS. Thanks to the proposed configuration, the output voltage of the components can be upgraded to MVDC, while reducing the number of power converters compared with other configurations without ZSC., This work was partially supported by Spain's Ministerio de Ciencia, Innovaci ' on y Universidades (MCIU), Agencia Estatal de Investigaci ' on (AEI) and Fondo Europeo de Desarrollo Regional (FEDER) Uni ' on Europea (UE) (grant number RTI2018-095720-B-C32), by the Federal Center for Technological Education of Minas Gerais, Brazil (process number 23062-010087/2017-51) and by the National Council of Technological and Scientific Development (CNPq-Brazil).
RODIN. Repositorio de Objetos de Docencia e Investigación de la Universidad de Cádiz
Publicación Artículo científico (JournalArticle)

Supervisory Control System for a Grid-Connected MVDC Microgrid Based on Z-Source Converters With PV, Battery Storage, Green Hydrogen System and Charging Station of Electric Vehicles

  • García Triviño, Pablo
  • De Oliveira-Asís, Lais
  • Soares-Ramos, Emanuel P. P.
  • Sarrias Mena, Raúl
  • García Vázquez, Carlos Andrés
  • Fernández Ramírez, Luis Miguel
This paper presents a new supervisory control system (SCS) designed to maintain the power balance and obtain economic benefit by selling energy to the grid in a microgrid based on Z-source converters (ZSCs) with renewable energy, energy storage systems (ESSs), and charging station for electric vehicles (EV) connected to a medium voltage direct current (MVDC) link. The main components of the microgrid are a photovoltaic (PV) system, battery (BAT) and green hydrogen system with a fuel cell (FC), electrolyzer (LZ) and hydrogen tank as ESSs, a local grid connection and two units of fast chargers for EVs. Owing to the proposed configuration, the output voltages of the components can be adapted to the MVDC to control their output power and reduce the number of power converters compared to the common configuration without ZSCs. Thus, the configuration by itself and the SCS can be considered the main novelties of this paper. The simulation results and the hardware-in-the-loop tests show that the proposed system (ZSC-based configuration and SCS) is perfectly valid for the microgrid, and confirm the proper operation of the SCS to achieve an economic benefit from the use of the grid.
RODIN. Repositorio de Objetos de Docencia e Investigación de la Universidad de Cádiz
Publicación Proyecto fin de carrera (BachelorThesis)

Averaged Dynamic Modeling and Control of a Quasi-Z-Source Inverter for Wind Power Applications

  • Soares-Ramos, Emanuel P. P.
  • De Oliveira-Assis, Lais
  • Sarrias Mena, Raúl
  • García Triviño, Pablo
  • García Vázquez, Carlos Andrés
  • Fernández Ramírez, Luis Miguel
Typically, permanent magnet synchronous generator (PMSG)-driven wind turbines (WTs) present a two-stage power converter topology based on a DC/DC boost converter and voltage source inverter. In this study, this configuration is substituted by a quasi-Z-source inverter (qZSI), which is an attractive solution for boosting and converting the voltage from DC to AC in a single stage. A 2 MW PMSG WT with qZSI was studied herein. A switched dynamic model (SDM) of the qZSI (including the modeling of all switches and firing pulses) is not recommended for steady-state stability studies, long-term simulations, or large electric power systems. For such studies, two averaged dynamic models are proposed in this work. Both models present the same control system as the SDM, except for the generation of firing pulses, which is not necessary in the averaged models. The two proposed models were evaluated and compared with the SDM in the large-scale WT under different operating conditions, such as wind speed fluctuations, variable power references, and grid disturbances (voltage sag and 3(rd) and 5(th) order harmonics injection), in order to demonstrate their adequacy to represent the system response with a high reduction in the simulation time and computational efforts., This work was supported in part by the Spain's Ministerio de Ciencia, Innovacion y Universidades (MCIU), Agencia Estatal de Investigacion (AEI), and Fondo Europeo de Desarrollo Regional (FEDER) Union Europea (UE) under Grant RTI2018-095720-B-C32, in part by the National Council of Technological and Scientific Development (CNPq), Brazil, in part by the Federal Center for Technological Education of Minas Gerais, Brazil, under Process 23062-010087/2017-51, and in part by the Regional Ministry of Economic Transformation, Industry, Knowledge and Universities of Junta de Andalucia under Grant PY20_00317.
RODIN. Repositorio de Objetos de Docencia e Investigación de la Universidad de Cádiz
Publicación Artículo científico (JournalArticle)

Simplified model of battery energy-stored quasi-Z-source inverter-based photovoltaic power plant with Twofold energy management system

  • De Oliveira-Assis, Lais
  • Soares-Ramos, Emanuel P. P.
  • Sarrias Mena, Raúl
  • Sarrias Mena, Raúl
  • García Triviño, Pablo
  • González Rivera, Enrique
  • Sánchez Sainz, Higinio
  • Llorens Iborra, Francisco
  • Fernández Ramírez, Luis Miguel
The use of a battery energy-stored quasi-Z-source inverter (BES-qZSI) for large-scale PV power plants exhibits promising features due to the combination of qZSI and battery as energy storage system, such as single-stage power conversion (without additional DC/DC boost converter), improvements in the output waveform quality (due to the elimination of switching dead time), and continuous and smooth delivery of energy to the grid (through the battery energy storage system). This paper presents a new simplified model of a BES-qZSI to represent the converter dynamics with sufficient accuracy while using a less complex model than the detailed model (including the modelling of all switches and switching pulses). It is based on averaged values of the variables, voltage/current sources, and the same control circuit than the detailed model, except for the switching pulses generation. The simplified model enables faster time-domain simulation and is useful for control design and dynamic analysis purposes. Additionally, an energy management system has been developed to govern the power supply to grid under two possible scenarios: 1) System operator command following; or 2) economic dispatch of the stored energy. The results obtained from simulations and experimental hardware-in-the-loop (HIL) setup for different operating conditions of the grid-connected large-scale PV power plant with battery energy storage under study demonstrate the validity of the proposed simplified model to represent the dynamics of the converter and PV power plant for steady-state stability studies, long-term simulations, or large electric power systems. © 2021 The Authors, This work was partially supported by the Spain's Ministerio de Ciencia, Innovaci?n y Universidades (MCIU), Agencia Estatal de Investigaci?n (AEI), and Fondo Europeo de Desarrollo Regional (FEDER) Uni?n Europea (UE) (grant number RTI2018-095720-B-C32), by the Federal Center for Technological Education of Minas Gerais, Brazil (process number 23062?010087/2017-51) and by the National Council of Technological and Scientific Development (CNPq-Brazil)
RODIN. Repositorio de Objetos de Docencia e Investigación de la Universidad de Cádiz
Publicación Artículo científico (JournalArticle)

Model Predictive Control-Based Optimized Operation of a Hybrid Charging Station for Electric Vehicles

  • González Rivera, Enrique
  • García Triviño, Pablo
  • Sarrias Mena, Raúl
  • Torreglosa, Juan P.
  • Jurado, Francisco
  • Fernández Ramírez, Luis Miguel
This paper presents an energy management system (EMS) based on a novel approach using model predictive control (MPC) for the optimized operation of power sources in a hybrid charging station for electric vehicles (EVs). The hybrid charging station is composed of a photovoltaic (PV) system, a battery, a complete hydrogen system based on a fuel cell (FC), electrolyzer (EZ), and tank as an energy storage system (ESS), grid connection, and six fast charging units, all of which are connected to a common MVDC bus through Z-source converters (ZSC). The MPC-based EMS is designed to control the power flow among the energy sources of the hybrid charging station and reduce the utilization costs of the ESS and the dependency on the grid. The viability of the EMS was proved under a long-term simulation of 25 years in Simulink, using real data for the sun irradiance and a European load profile for EVs. Furthermore, this EMS is compared with a simpler alternative that is used as a benchmark, which pursues the same objectives, although using a states-based strategy. The results prove the suitability of the EMS, achieving a lower utilization cost (-25.3%), a notable reduction in grid use (-60% approximately) and an improvement in efficiency.
RODIN. Repositorio de Objetos de Docencia e Investigación de la Universidad de Cádiz
Publicación Artículo científico (JournalArticle)

Optimal online battery power control of grid-connected energy-stored quasi-impedance source inverter with PV system

  • García Triviño, Pablo
  • Sarrias Mena, Raúl
  • García Vázquez, Carlos Andrés
  • Leva, Sonia
  • Fernández Ramírez, Luis Miguel
This study presents an optimal online control that implements a biogeography-based optimization (BBO) algorithm on a battery energy system (BES) integrated into an energy-stored quasi-impedance source inverter (qZSI) that connects a photovoltaic (PV) power plant to the grid. The BBO algorithm was used to tune the PI regulator in the BES current control loop by minimizing the integral time absolute error (ITAE). Two different options for the BBO are compared in this application:1) a PI controller with online self-tuning based on BBO, and 2) a PI controller with offline tuning using BBO. Moreover, the BBO-based PI controllers were compared with a third controller tuned online using the particle swarm optimization (PSO) algorithm. To evaluate and compare the controllers, a PV power plant with a battery energy-stored qZSI was simulated under different operating conditions, such as step changes in the BES current reference, different sun irradiance, and a grid voltage sag. The results demonstrate better control of the BES current with the online tuning techniques (BBO and PSO) than with the offline tuning procedure, and similar results between the two online tuning algorithms. Nevertheless, throughout the simulation, the time of use of the BBO algorithm was almost 2.5 times smaller than the PSO algorithm. Therefore, the online BBO-based PI controller is considered the most suitable option.
RODIN. Repositorio de Objetos de Docencia e Investigación de la Universidad de Cádiz
Publicación Artículo científico (JournalArticle)

Hydrogen based configurations for an overhead crane with quasi-Z-source inverter

  • García Triviño, Pablo
  • Sarrias Mena, Raúl
  • García Vázquez, Carlos Andrés
  • Llorens Iborra, Francisco
  • Sánchez Sainz, Higinio
  • Fernández Ramírez, Luis Miguel
Most of the overhead cranes used to date are powered by diesel engine or electrical grid and voltage source inverter. The economic and environmental costs of fossil fuels, and the unsteady price of electricity, encourage exploring new applications for developing electric power technologies. In this scenario, the main objective of this paper is to analyze the technical and economic feasibility of two new configurations based on hydrogen system and quasi-Z-source inverter (qZSI) for an overhead crane. The first configuration uses a fuel cell (FC) connected to a qZSI to supply the crane. The second one integrates an electrolyzer (LZ) as an energy storage system (ESS) into the impedance network of the qZSI (without additional DC/DC converter), which allows to recover energy during the regenerative braking of the crane and use it to produce hydrogen. The modelling and control are described, and short simulations of the working cycle of the crane under different initial hydrogen tank levels, and long simulations with several working cycles, are considered. The results show the technical viability of the two hydrogen-based configurations and the control systems implemented, since they can power the crane under all the situations studied. Nevertheless, the configuration with FC and LZ presents a higher energy efficiency (65% vs 44% with the FC-only configuration). Regarding the economic study, both configurations are compared with a diesel-based and with a full-electric configuration powered by the grid. Analyzing both hydrogen-based configurations, the results show that the configuration with FC and FZ becomes more profitable after 1.56 years, despite the higher initial cost. However, both configurations result more expensive than those based on diesel engine and fully powered by the grid. The two proposed configurations would be more cost-effective than the initial configuration in a plausible future with a 40% decrease in hydrogen cost, 14 páginas
RODIN. Repositorio de Objetos de Docencia e Investigación de la Universidad de Cádiz
Publicación Artículo científico (JournalArticle)

Transformer‐Based Z‐Source Inverter with MVDC Link

  • González Rivera, Enrique
  • García Vázquez, Carlos Andrés
  • García Triviño, Pablo
  • Sarrias Mena, Raúl
  • Jurado, Francisco
  • Sainz, Luis
  • Bogarra, Santiago
  • Córcoles, Felipe
  • Fernández Ramírez, Luis Miguel
Z‐source inverters have attracted considerable attention in renewable energy systems like photovoltaic (PV) systems due to advantages such as buck–boost power conversion in single stage, shoot-through capability, and wide range of input voltage regulation. Transformer-Based Z-source inverters (TransZSI) based on magnetically coupled inductors and reduced number of passive components can be used to improve the boost capacity of these inverters, and to increase the voltage levels. Medium voltage DC (MVDC) is being used more and more in distribution grids and renewable energy systems. This paper presents a transZ-source inverter with MVDC link where renewable energy systems and energy storage systems can be integrated. The active and reactive powers and DC voltage are controlled by acting on the modulation index and shoot-through duty cycle of the converter. The trans-Z-source inverter is evaluated under different operating conditions to illustrate its suitable operation. © 2022, European Association for the Development of Renewable Energy, Environment and Power Quality (EA4EPQ). All rights reserved.