COMPORTAMIENTO RESISTENTE FRENTE A ALTAS TEMPERATURAS DE PERFILES TUBULARES DE ACERO RELLENOS DE HORMIGON DE ALTA RESISTENCIA

BIA2009-09411

•
Funding agency name Ministerio de Ciencia e Innovación
Funding agency acronym MICINN
Program Programa Nacional de Proyectos de Investigación Fundamental
Subprogram Subprograma de Proyectos de Investigación Fundamental no Orientada
Call Proyectos I+D
Call year 2009
State Plan 2008-2011 Plan Nacional de Investigación Científica, Desarrollo e Innovación Tecnológica
Management unit Subdirección General de Proyectos de Investigación
Beneficiary centre UNIVERSITAT POLITÈCNICA DE VALÈNCIA

Resultados relacionados

Resultados totales (Incluyendo duplicados): 13
Encontrada(s) 1 página(s)

RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publication Artículo científico (JournalArticle)

Fire design method for bar-reinforced circular and elliptical concrete filled tubular columns

  • Espinós Capilla, Ana|||0000-0001-7335-4676
  • Romero, Manuel L.|||0000-0001-5247-4767
  • Hospitaler Pérez, Antonio|||0000-0001-7108-3104
A method for calculating the design axial buckling load in the fire situation of unreinforced axially loaded concrete filled circular hollow section columns was presented by the authors in a previous paper [1]. In the present paper, the method is extended to bar-reinforced columns of circular and elliptical cross-section, as a necessary continuation to complete the proposal. The method presented here is based on the guidelines of Clause 4.3.5.1 in Eurocode 4 Part 1.2 for the fire design of composite columns and is developed on the basis of the results of new parametric studies, with varying values of the outer diameter of the column, steel tube wall thickness, relative slenderness, percentage of reinforcement and fire exposure time. From the results of these parametric studies, appropriate expressions and tables for the different parts which integrate the design method are derived. The proposed method is valid for centrally loaded bar-reinforced circular and elliptical concrete filled tubular columns, with a maximum percentage of reinforcement of a 5% and makes allowance for columns with a high slenderness, extending the current limits of Eurocode 4 Part 1.2., The authors would like to express their sincere gratitude to the Spanish "Ministerio de Ciencia e Innovacion" for the help provided through the Project BIA2009-9411 and to the European Union through the FEDER funds.
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publication Artículo científico (JournalArticle)

Simple calculation model for evaluating the fire resistance of unreinforced concrete filled tubular columns

  • Espinós Capilla, Ana|||0000-0001-7335-4676
  • Romero, Manuel L.|||0000-0001-5247-4767
  • Hospitaler Pérez, Antonio|||0000-0001-7108-3104
This paper presents a method for calculating the fire resistance of unreinforced axially loaded concrete filled circular hollow section columns, based on the guidelines of Eurocode 4 Part 1.2 for the fire design of composite columns. The different design approaches which are currently available worldwide are reviewed in this paper, focusing in particular on the European code, which is discussed and analysed in depth. Several of the aspects which are nowadays missing or thought to be arguable by researchers in the Eurocode 4 method are studied and on the basis of parametric studies a new proposal is developed, so that designers can easily apply the code in the future. The parametric studies investigate the main factors affecting the fire resistance of unreinforced concrete filled tubular (CFT) columns, such as the outer diameter, the thickness of the steel tube wall, the relative slenderness of the column at room temperature and the fire exposure time, widely covering the range of values which can be found in practice. From the results of these parametric studies, equations for obtaining the equivalent temperatures of steel and concrete are developed, and appropriate flexural stiffness reduction coefficients are integrated in the simple calculation model of Eurocode 4. The method presented here is valid for centrally loaded circular CFT columns filled with unreinforced normal strength concrete, and makes possible the calculation of slender columns, extending the current limitations in buckling length of the European code, The authors would like to express their sincere gratitude to the Spanish "Ministerio de Ciencia e Innovacion" for the help provided through the Project BIA2009-9411 and to the European Union through the FEDER funds.
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publication Artículo científico (JournalArticle)

Advanced model for predicting the fire response of concrete filled tubular columns

  • Espinós Capilla, Ana|||0000-0001-7335-4676
  • Romero, Manuel L.|||0000-0001-5247-4767
  • Hospitaler Pérez, Antonio|||0000-0001-7108-3104
In this work, a nonlinear finite element three-dimensional model is presented and validated in order to study the behaviour of axially loaded concrete filled tubular (CFT) columns with circular cross-section exposed to fire. A realistic sequentially coupled nonlinear thermal-stress analysis is conducted for a series of columns available in the literature. The model is validated by comparing the simulation results with the real fire resistance tests. By means of this model, and extensive sensitivity analysis is performed over a wide range of aspects concerning the finite element modelling of the problem under study, including new key factors not studied previously. Based on this sensitivity analysis several modelling recommendations are given in this paper, which will be useful for future research work. The validated numerical model is furthermore employed to study and discuss the Eurocode 4 Part 1-2 simple calculation model, which is deeply analysed in this paper., The authors express their sincere gratitude to the Spanish "Ministerio de Ciencia e Innovacion" for the help provided through the Project BIA2009-9411 and to the European Union through the FEDER funds.
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publication Artículo científico (JournalArticle)

Influence of ultra-high strength infill in slender concrete-filled steel tubular columns

  • Portoles Flaj, José Manuel
  • Serra Mercé, Enrique
  • Romero, Manuel L.|||0000-0001-5247-4767
This paper describes 24 tests conducted on slender circular tubular columns filled with normal, high, and ultra-high strength concrete for plain, bar reinforced and steel fiber reinforced columns. These were reinforced and subjected to both concentric and eccentric axial load. It is a continuation of a previous research paper (Portoles et al., 2011 [1]), which presented test results on eccentrically loaded plain concrete columns. The test parameters are nominal strength of concrete (30, 90 and 130 MPa), eccentricity e (0, 20 and 50 mm) and type of reinforcement. A comparison with the corresponding empty tubular columns is performed, as the aim of the paper is to analyze the influence of each type of infill and establish the best option for practical application. For the limited cases analyzed the results show that the addition of high or ultra-high strength infill is more useful for concentric loaded cases than for eccentric loaded ones, where it seems that the best design option is the utilization of bar reinforced concrete filling rather than steel fiber to reinforce CFST columns. The experimental ultimate load of each test was compared with the design loads from Eurocode 4, accurate for the eccentrically loaded tests., The authors wish to express their sincere gratitude to the Spanish Ministry of Science and Innovation for help provided through project BIA 2009_09411, Plan E, and to the European Community for FEDER funds,
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publication Artículo científico (JournalArticle)

Fire behaviour of concrete filled elliptical steel columns

  • Espinós Capilla, Ana|||0000-0001-7335-4676
  • Hospitaler Pérez, Antonio|||0000-0001-7108-3104
  • Gardner, Leroy
  • Romero, Manuel L.
In this work, a non-linear three-dimensional finite element model is presented in order to study the behaviour of axially loaded concrete filled elliptical hollow section (CFEHS) columns exposed to fire. This study builds on previous work carried out by the authors on concrete filled circular hollow section (CFCHS) columns both at room temperature and in fire. The numerical model is first validated at room temperature against a series of experiments on CFEHS stub columns available in the literature and subsequently extended to study the performance of slender columns at elevated temperatures. The aim of this work is to understand and represent the behaviour of axially loaded CFEHS columns in fire situations and to compare their effectiveness with that of the circular concrete filled tubular (CFT) columns. Parametric studies to explore the influence of variation in global member slenderness, load level, cross-section slenderness and section size are presented. Finally, guidance on the fire design of CFEHS columns is proposed: it is recommended to follow the guidelines of Clause 4.3.5.1 in EN 1994-1-2, but employing the flexural stiffness reduction coefficients established in the French National Annex with an equivalent EHS diameter equal to P/¿, where P is the perimeter of the ellipse., The authors would also like to acknowledge Universidad Politecnica de Valencia for providing fellowship funding for the first author's stay as a visiting academic at Imperial College London.
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publication Artículo científico (JournalArticle)

Simulation and design recommendations of eccentrically loaded slender concrete-filled tubular columns

  • Portoles Flaj, José Manuel
  • Romero, Manuel L.
  • Filippou, Filip C.
  • Bonet Senach, José Luís|||0000-0002-6687-5307
This paper proposes an efficient numerical model for the simulation of the behavior of slender circular concrete-filled tubular columns subjected to eccentric axial load with single curvature, for the cases of both normal and high strength concrete. The paper focuses on the study of the influence that the variables affecting beam–column behavior (length and relative slenderness) and the variables affecting section behavior (diameter/thickness ratio, mechanical capacity of steel) have on the overall buckling of this type of column. An extended parametric study is carried out to propose design recommendations, primarily to establish the importance of the use of high strength concrete compared with that of normal strength concrete. The results show that for slender elements the optimum design is reached when the mechanical capacity of the steel is slightly lower than that of the concrete contribution., The authors wish to express their sincere gratitude to the Spanish "Ministerio de Educacion" for help provided with project BIA2005_255, and to the Spanish "Ministerio de Ciencia e Innovacion" with project BIA2009-09411, to the European Community for FEDER funds, and to the Fundacio Caixa Castello-Bancaixa.
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publication Artículo científico (JournalArticle)

Fire behavior of axially loaded slender high strength concrete-filled tubular columns

  • Romero, Manuel L.|||0000-0001-5247-4767
  • Espinós Capilla, Ana|||0000-0001-7335-4676
  • Ibáñez, Carmen|||0000-0002-9354-5637
  • Hospitaler Pérez, Antonio|||0000-0001-7108-3104
  • Moliner, V.
This paper describes sixteen fire tests conducted on slender circular hollow section columns filled with normal and high strength concrete, subjected to concentric axial loads. The test parameters were the nominal strength of concrete (30 and 80 MPa), the infilling type (plain concrete, reinforced concrete and steel fiber reinforced concrete) and the axial load level (20% and 40%). The columns were tested under fixed-pinned boundary conditions and the relative slenderness at room temperature was higher than 0.5 in all of the cases. A numerical model was validated against the tests, in order to extend the results and understand the failure mode of such columns. It is the aim of this paper to study the influence in a fire situation of the use of high strength concrete, as opposed to normal strength concrete. The results have shown that for slender columns subjected to high temperatures, the behavior of high strength concrete was different than for stub columns, spalling not being observed in the experiments. Furthermore, the addition of steel fibers was not found very advantageous in slender columns, since no increment in terms of fire resistance was obtained for the columns which used this type of reinforcement. However, the addition of reinforcing bars seems to be the solution in some cases, where the use of external fire protection wants to be avoided in the design of HSS structures, since the reinforcing bars allow the tube to resist a higher axial load, The authors wish to express their sincere gratitude to the Spanish Ministry of Science and Innovation for help provided through project BIA 2009_09411, and to the European Community for the FEDER funds.
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publication Artículo científico (JournalArticle)

Influence of Slenderness on High-Strength Rectangular Concrete-Filled Tubular Columns with Axial Load and Nonconstant Bending Moment

  • Hernández Figueirido, David
  • Romero, Manuel L.|||0000-0001-5247-4767
  • Bonet Senach, José Luís|||0000-0002-6687-5307
  • Montalva-Subirats, Jose-Miguel|||0000-0002-1855-9596
Forty-nine experimental tests were conducted on rectangular and square tubular columns filled with high-strength concrete (f'(c) 590 MPa) subjected to axial load and a nonconstant bending moment distribution. The test parameters were the length (2, 3, and 4 m), the cross-section aspect ratio (square or rectangular), the wall thickness (4 or 5 mm), and the ratio of the top and bottom first-order eccentricities r = e(top)/e(bottom) (1, 0.5, 0, and -0.5). The effect of slenderness combined with the influence of variable curvature is compared with the design loads from AISC 360-10 and Eurocode 4. The results show that, for the slender elements of this experimental campaign, both codes present a similar error close to 4%. The small error margin indicates that both standards are applicable to high-strength concrete, although the concrete tested is outside the upper bond of Eurocode 4 and AISC's specifications. However, there are particular cases that present excessive unsafe errors. These errors correspond to the cases where the second-order effects are more important and are attributable to an overestimation of the flexural stiffness E x I, which indicates that it needs correction. DOI: 10.1061/(ASCE)ST.1943-541X.0000590. (C) 2012 American Society of Civil Engineers., The authors express their gratitude to the Spanish Ministry of Science and Innovation for help provided through Grant No. BIA2009_9411, to the Spanish Ministry of Education through Grant No. BIA2005-255, and the European Union for FEDER Funds.
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publication Artículo científico (JournalArticle)

Comparison of a Three-Dimensional Numerical Model for Fire Resistance of Axially Loaded Concrete Filled Steel Tubular Columns with Eurocode 4

  • Espinós Capilla, Ana|||0000-0001-7335-4676
  • Ibáñez, Carmen|||0000-0002-9354-5637
  • Romero, Manuel L.|||0000-0001-5247-4767
  • Hospitaler Pérez, Antonio|||0000-0001-7108-3104
[EN] In this paper, the behaviour of slender axially loaded square and circular CFT columns exposed to fire is modelled using the finite element analysis package ABAQUS. A realistic sequentially coupled nonlinear thermal-stress analysis is conducted for a series of columns available in the literature. By means of this model, a comparison between fire resistance simulations results and experimental tests found in literature is made. Similarly, simulations results are compared to the Eurocode 4 simplified calculation model predictions. Comparisons show that whereas Eurocode 4 predictions are very conservative for both circular and square section CFT columns, the results obtained from the developed numerical model are much more realistic., The authors express their sincere gratitude to the Spanish “Ministerio de Ciencia e Innovación” for the help provided through the Project BIA2009-9411 and to the European Union through the FEDER funds.
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publication Artículo científico (JournalArticle)

Experimental study of high strength concrete-filled circular tubular columns under eccentric loading

  • Portoles, J.M.
  • Filippou, F.C.
  • Romero, Manuel L.|||0000-0001-5247-4767
  • Bonet Senach, José Luís|||0000-0002-6687-5307
The paper describes 37 tests conducted on slender circular tubular columns filled with normal and high strength concrete subjected to eccentric axial load. The test parameters were the nominal strength of concrete (30, 70 and 90 MPa), the diameter to thickness ratio Dt, the eccentricity ratio eD and the column slenderness (LD). The experimental ultimate load of each test was compared with the design loads from Eurocode 4, which limits the strength of concrete up to 50 MPa. The aim of the paper is to establish the advisability of the use of high strength concretes as opposed to that of normal strength concretes by comparing three performance indices: concrete contribution ratio, strength index and ductility index. The results show for the limited cases analyzed that the use of high strength concrete for slender composite columns is interesting since this achieves ductile behavior despite the increase in load-carrying capacity is not greatly enhanced. © 2010 Elsevier Ltd. All rights reserved., The authors wish to express their sincere gratitude to the Spanish Ministry of Education for help provided through project BIA2005_255 and BIA 2009_09411, to the European Community for FEDER funds, and to the Fundacio Caixa Castello-Bancaixa.
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publication Artículo científico (JournalArticle)

Fiber beam model for fire response simulation of axially loaded concrete filled tubular columns

  • Ibáñez, Carmen|||0000-0002-9354-5637
  • Romero, Manuel L.|||0000-0001-5247-4767
  • Hospitaler Pérez, Antonio|||0000-0001-7108-3104
This paper presents a fiber beam model for the fire response simulation of concrete filled tubular columns of circular section under concentric axial load. The model consists of two parallel components, one with a circular tubular steel section, and the other with a solid circular concrete section. The components interact with nonlinear longitudinal and transverse links at the end nodes. The element is formulated on a system without rigid body modes and accounts for large displacement geometry through the co-rotational formulation connected both longitudinally and transversely at their nodes by link elements. The model is capable of representing different types of concrete infill of the steel tubes: plain, reinforced and steel fiber reinforced concrete of normal or high strength. It is validated against experimental data from column specimens under fire. The results are also compared against a three-dimensional finite element model characterized by its accuracy of fire response simulation., The authors express their sincere gratitude to Prof. Filip C. Filippou for his comments to the paper. Also to the Spanish "Ministerio de Ciencia e Innovacion" for the help provided through the Project BIA2009-9411; to the Valencian autonomous community institution "Generalitat Valenciana" for the support given by means of the ACIF/2010/219 Program; and to the European Union for its collaboration through the FEDER funds.
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publication Artículo científico (JournalArticle)

Ultimate capacity of rectangular concrete-filled steel tubular columns under unequal load eccentricities

  • Hernández Figueirido, David
  • Romero, Manuel L.|||0000-0001-5247-4767
  • Bonet Senach, José Luís|||0000-0002-6687-5307
  • Montalva-Subirats, Jose-Miguel|||0000-0002-1855-9596
The paper describes 36 experimental tests conducted on rectangular and square tubular columns filled with normal and high strength concrete and subjected to a non-constant bending moment distribution with respect to the weak axis. The test parameters were the nominal strength of concrete (30 and 90 MPa), the cross-section aspect ratio (square or rectangular), the thickness (4 or 5 mm) and the ratio of the top and bottom first order eccentricities e top/e bottom (1, 0.5, 0 and - 0.5). The ultimate load of each test was compared with the design loads from Eurocode 4, presenting unsafe results inside a 10% safety margin. The tests show that the use of high strength concrete is more useful for the cases of non-constant bending moment, whereas if the aim is to obtain a more ductile behavior the use of concrete-filled columns is more appealing in the cases of normal strength concrete with non-constant bending moments because, although they resist less axial force than the members with HSC, they obtain a softened post-peak behavior. © 2011 Elsevier Ltd., The authors wish to express their sincere gratitude to the Spanish Ministry of Education for the help provided through projects BIA2005_255 and BIA2009_9411, and to the European Community for FEDER funds.
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publication Artículo científico (JournalArticle)

Fire behavior of eccentrically loaded slender high strength concrete-filled tubular columns

  • Moliner, Vicente
  • Espinós Capilla, Ana|||0000-0001-7335-4676
  • Romero, Manuel L.|||0000-0001-5247-4767
  • Hospitaler Pérez, Antonio|||0000-0001-7108-3104
This paper describes sixteen fire tests conducted on slender circular hollow section columns filled with normal and high strength concrete, subjected to concentric axial loads. The test parameters were the nominal strength of concrete (30 and 80 MPa), the infilling type (plain concrete, reinforced concrete and steel fiber reinforced concrete) and the axial load level (20% and 40%). The columns were tested under fixed-pinned boundary conditions and the relative slenderness at room temperature was higher than 0.5 in all of the cases. A numerical model was validated against the tests, in order to extend the results and understand the failure mode of such columns. It is the aim of this paper to study the influence in a fire situation of the use of high strength concrete, as opposed to normal strength concrete. The results have shown that for slender columns subjected to high temperatures, the behavior of high strength concrete was different than for stub columns, spalling not being observed in the experiments. Furthermore, the addition of steel fibers was not found very advantageous in slender columns, since no increment in terms of fire resistance was obtained for the columns which used this type of reinforcement. However, the addition of reinforcing bars seems to be the solution in some cases, where the use of external fire protection wants to be avoided in the design of HSS structures, since the reinforcing bars allow the tube to resist a higher axial load., The authors wish to express their sincere gratitude to the Spanish Ministry of Science and Innovation for the help provided through project BIA 2009_09411, to the Generalitat Valenciana for the IMPIVA funds in the framework of the project FUEGOSTRUCT and to the European Community for the FEDER funds.