Efficiency improvement of a ground coupled heat pump system from energy management
The installed capacity of an air conditioning system is usually higher than the average cooling or heating
demand along the year. So, most of the time, the system is working under its actual capacity. In this
contribution, we study the way to improve the efficiency of a ground coupled heat pump air conditioning
system by adapting its produced thermal energy to the actual thermal demand. For this purpose, an air
conditioning system composed by a ground coupled heat pump and a central fan coil linked to an office
located in a cooling dominated area was simulated, and a new management strategy aiming to diminish
electrical consumption was developed under the basic constraint that comfort requirements are kept.
This strategy takes advantage of the possibility of managing the air flow in the fan, the water mass flows
in the internal and external hydraulic systems, and the set point temperature in the heat pump to
achieve this objective. The electrical consumption of the system is calculated for the new management
strategy and compared with the results obtained for a conventional one, resulting in estimated energy
savings around 30%, This work has been supported by the Spanish Government under projects "Modelado y simulacion de sistemas energeticos complejos" (2005 Ramon y Cajal program), "Modelado, simulacion y validacion experimental de la transferencia de calor en el entorno de la edificacion" (ENE2008-0059/CON). A. Sala is grateful to the financial support of grants DPI2008-06731-c02-01 (Spanish Government), and Generalitat Valenciana Prometeo/2008/088.