Pasar al contenido principal

INTEGRACION DE FUENTES DE ENERGIA RENOVABLES Y CONTROL DE FLUJOS DE POTENCIA EN REDES HVDC MEDIANTE CONVERTIDORES MODULARES MULTI-NIVEL

DPI2014-53245-R

•
Nombre agencia financiadora Ministerio de Economía y Competitividad
Acrónimo agencia financiadora MINECO
Programa Programa Estatal de I+D+i Orientado a los Retos de la Sociedad
Convocatoria Proyectos I+D+i Retos de Investigación
Año convocatoria 2014
Plan Estatal 2013-2016 Plan Estatal de Investigación Científica y Técnica y de Innovación
Unidad de gestión Secretaría de Estado de Educación, Formación Profesional y Universidades
Centro beneficiario UNIVERSITAT POLITÈCNICA DE VALÈNCIA
Identificador persistente http://dx.doi.org/10.13039/501100003329

Resultados relacionados

Resultados totales (Incluyendo duplicados): 12
Encontrada(s) 1 página(s)

RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publicación Contribución de congreso (ConferenceOutput)

Mixed Grid-Forming and Grid-Following Wind Power Plants for Black Start Operation

  • Martínez-Turégano, Jaime|||0000-0002-3483-8253
  • Añó Villalba, Salvador Conrado|||0000-0002-8435-5225
  • Bernal-Perez, Soledad|||0000-0002-5431-9792
  • Blasco-Gimenez, Ramon|||0000-0003-3427-1581
  • Peña, R.
Grid forming wind turbines allow for additional services to be provided by wind power plants. These additional services include self-start operation, islanding operation of offshore ac-grids and contribution to system restoration after a black-out. As the complete electric system will consist of both grid-following and grid-forming wind power plants, the aim of this paper is to study possible interactions between grid forming and grid following wind turbines during black-start operation. The presented case study includes a 400 MW off-shore wind power plant connected by means of a 75km HVac cable to the on-shore transmission grid. The results show adequate islanded and black-start operation with less than 25% grid forming power., The authors would like to thank the support of the Spanish Ministry of Economy and EU FEDER Funds under grant DPI2014-53245-R. This project has received funding from the European Union¿s Horizon 2020 research and innovation program under grant agreement No. 691714.
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publicación Artículo científico (JournalArticle)

Aggregation of Type-4 Large Wind Farms Based on Admittance Model Order Reduction

  • Martínez-Turégano, Jaime|||0000-0002-3483-8253
  • Añó Villalba, Salvador Conrado|||0000-0002-8435-5225
  • Bernal-Perez, Soledad|||0000-0002-5431-9792
  • Blasco-Gimenez, Ramon|||0000-0003-3427-1581
[EN] This paper presents an aggregation technique based on the resolution of a multi-objective optimization problem applied to the admittance model of a wind power plant (WPP). The purpose of the presented aggregation technique is to reduce the order of the wind power plant model in order to accelerate WPP simulation while keeping a very similar control performance for both the simplified and the detailed models. The proposed aggregation technique, based on the admittance model order reduction, ensures the same DC gain, the same gain at the operating band frequency, and the same resonant peak frequency as the detailed admittance model. The proposed aggregation method is validated considering three 400-MW grid-forming Type-4 WPPs connected to a diode rectifier HVDC link. The proposed aggregation technique is compared to two existing aggregation techniques, both in terms of frequency and time response. The detailed and aggregated models have been tested using PSCAD-EMTsimulations, with the proposed aggregated model leading to a 350-fold reduction of the simulation time with respect to the detailed model. Moreover, for the considered scenario, the proposed aggregation technique offers simulation errors that are, at least, three-times smaller than previously-published aggregation techniques., The authors would like to thank the support of the Spanish Ministry of Science, Innovation and Universities and EU FEDER funds under Grants DPI2014-53245-R and DPI2017-84503-R. This project has received funding from the European Union's Horizon 2020 research and innovation program under Grant Agreement No. 691714
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publicación Artículo científico (JournalArticle)

Automatic under-frequency load shedding mal-operation in power systems with high wind power penetration

  • Aparicio Marín, Nestor
  • Belenguer Balaguer, Enrique
  • Añó Villalba, Salvador Conrado|||0000-0002-8435-5225
  • Blasco-Gimenez, Ramon|||0000-0003-3427-1581
[EN] Countries with a limited interconnection capacity suffer substantial frequency variations after large incidents so they use automatic under-frequency load shedding schemes to arrest the frequency decay. Some of these countries such as Portugal, Spain and Ireland also have very high wind penetrations. This can cause additional frequency excursions due to generation time variability but also to the fact that variable speed wind turbines do not add directly their inertia to the power system. Thus several transmission system operators have announced new grid codes requiring wind turbines to provide frequency response. In some scenarios, however, wind energy support may be detrimental to frequency control because it generates an extra energy that reduces decay and derivative but that cannot be maintained over time. These lower values of frequency decay and derivative are currently expected after a reduced incident or when conventional generation, which can maintain the extra generation, provides frequency support, so lead to low or no load shedding. This paper has studied, in particular, the effect of wind generation emulating inertia. A reduction of frequency derivative is achieved, which looks positive at first, but in some cases leads to initial smaller load shedding than the incident requires. A reduced frequency derivative triggers less under-frequency relays as if there were a significant amount of conventional generation that is online. However, this generation has been substituted by wind generation emulating inertia, and as it can maintain extra generation over time, the frequency continues to decay until the shedding of the next load step. As a result there is an excessive frequency deviation and an incorrect load shedding for the magnitude of the initial disturbance. In order to prevent this problem, automatic under frequency load shedding settings may need readjustment when a large amount of wind generation provides frequency support. (C) 2017 International Association for Mathematics and Computers in Simulation (IMACS). Published by Elsevier B.V. All rights reserved., The present work was supported by the Spanish Ministry of Economy and Competitivity and European Union FEDER funds under grant DPI2014-53245-R and by the Universitat Jaume I through project number P1 . 1B2015-42. Part of this work was done by Nestor Aparicio during a visit to University College Dublin, which was supported by the Spanish Ministry of Education, Culture and Sport under grant Jose Castillejo CAS14/00384.
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publicación Artículo científico (JournalArticle)

A DC-DC Converter Based On Modified Flyback Converter Topology

  • Pesce, C.
  • Riedemann, J.
  • Andrade, I.
  • Peña, R.
  • Blasco-Gimenez, Ramon|||0000-0003-3427-1581
[EN] This paper proposes a DC-DC power converter topology based on a modified Flyback Converter (FC). The aim of the proposed topology is to increase the voltage gain by connecting the inputs of N isolated FCs in parallel and the N secondary inductances in series. This scheme reduces the current in each switch then reducing the associated losses. A single diode and an output capacitance complete the power converter circuit. A Proportional+Integral (PI) controller is used to control the output voltage with the converter operating in discontinuous current mode. The proposed converter can handle more power than the standard FC with a low number of active power devices. The system is modeled using PSIM platform and experimental results are presented considering a 1kW prototype., Este trabajo fue financiado por Universidad de La Frontera, Temuco, Chile, bajo el proyecto DIUFRO17-0044. También se agradece el aporte financiero entregado por Fondecyt Chile bajo el contrato 1151325 y CONICYT/FONDAP/15110019 y al Ministerio de Economía Español por el contrato DPI2014- 53245-R
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publicación Artículo científico (JournalArticle)

Small-signal stability and fault performance of mixed grid forming and grid following offshore wind power plants connected to a HVDC-diode rectifier

  • Martínez-Turégano, Jaime|||0000-0002-3483-8253
  • Añó Villalba, Salvador Conrado|||0000-0002-8435-5225
  • Bernal-Perez, Soledad|||0000-0002-5431-9792
  • Blasco-Gimenez, Ramon|||0000-0003-3427-1581
  • Peña, Rubén
[EN] This study aims at validating the simultaneous operation of grid following and grid forming wind power plants when connected to a common diode rectifier-based HVDC link. The controllers for both grid forming and grid following wind turbines include fault-ride-through capability with soft restoration of the off-shore AC-grid. Current and voltage controllers are developed in the stationary alpha beta reference frame. The presented control and soft restoration strategies are based on local measurements only and do not require communication between wind turbine generators. The small-signal stability analysis of the mixed system in multiple d-q axis using detailed string models is carried out in order to show the sensitivity to grid following phase-locked-loop gains and to grid forming droop gains. Interoperability between grid forming and grid following wind turbines during transients is shown by means of detailed simulation during symmetric faults in different locations of the off-shore grid., The authors would like to thank the support of the Spanish Ministry of Economy and EU FEDER funds under grants DPI2014-53245-R and DPI2017-84503-R. This project has received funding from the European Union's Horizon 2020 research and innovation program under grant agreement No. 691714. Project partially funded by the EU through the Comunitat Valenciana2014-2020 European Regional Development Fund (FEDER) OperatingProgram (grant IDIFEDER/2018/036). The support provided by Fondecyt project 1201616 and CONICYT/FONDAP/1511001 is kindly acknowledged. ANID support through grant ANID/FONDAP/15110019 is kindly acknowledged.
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publicación Artículo científico (JournalArticle)

Stability analysis of multi-terminal HVDC with diode rectifier connected off- shore wind power plants

  • Bernal-Perez, Soledad|||0000-0002-5431-9792
  • Añó Villalba, Salvador Conrado|||0000-0002-8435-5225
  • Blasco-Gimenez, Ramon|||0000-0003-3427-1581
[EN] This paper addresses the detailed modeling and small-signal stability analysis of a multi-terminal high voltage direct current (HVDC) system including a large diode rectifier-connected off-shore wind power plant (WPP). The study covers both islanded and connected WPP operation with different control scenarios. Islanded WPP stands for non-conducting HVDC diode rectifier (DR) whereas in connected WPP operation the DR is conducting. The study of both modes is important as the WPP would be in one of these modes during normal operation. Variable off-shore ac-grid frequency and a dynamic diode rectifier model have been considered for adequate dynamic modeling. The proposed models have been validated against detailed PSCAD EMT simulations and have been used to carry out the small-signal stability analysis of the islanded and connected WPP with different scenarios. Moreover, the dynamic model is used to assess the system robustness against parametric uncertainties, communication delay and power level, ensuring the integration of the off-shore WPP into the on-shore electrical power system. This study also points out that adequate droop control of the HVDC grid has a larger impact on overall stability than the diode rectifier connected off-shore WPP controllers., This work was supported by the Spanish Ministry of Economy and EU FEDER Funds under grants DPI2014-53245-R, and DPI2017-84503-R. This project has received funding from the European Union's Horizon 2020 research and innovation program under grant agreement No. 691714.
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publicación Artículo científico (JournalArticle)

A multilevel modular DC DC converter topology

  • Vidal, R.
  • Soto, D.
  • Andrade, I.
  • Riedemann, J.
  • Pesce, C.
  • Belenguer, E.
  • Pena, R.
  • Blasco-Gimenez, Ramon|||0000-0003-3427-1581
[EN] A multilevel modular DC DC power conversion topology based on cascaded H-Bridge converters in a double II configuration is presented. The topology is intended to interconnect large power DC networks. A two level control hierarchy is used to regulate the DC voltage of each H-bridge module. At the top level, DC and circulating AC currents are used to control the total energy converter in all branches (both parallels and series) of each II arrange. At bottom level, the voltage balance of a converter branch, which comprises N H-bridge modules, is carried out by balancing (N-1) capacitor voltage deviations, with respect to the average capacitor voltage. The entire topology and control strategies are simulated in a PSIM environment. Simulation results with three H-bridge converters per branch are shown and preliminary experimental results with a low power prototype are also included., This work was supported by Fondecyt grant 1151325, CONICYT/FONDAP/15110019, The Spanish Ministry of Economy and EU FEDER funds under grant DPI2014-53245-R, The University of Magallanes grant PR-FI-02IE14/15, Universitat Jaume I grant P1.1B2013-51, the Newton Picarte Project EPSRC:EP/N004043/1 and CONICYT DPI20140007.
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publicación Artículo científico (JournalArticle)

Embedded real-time simulators for electromechanical and power electronic systems using system-on-chip devices

  • Tormo, Daniel
  • Idkhajine, Laucine
  • Monmasson, Eric
  • Vidal-Albalate, Ricardo
  • Blasco-Gimenez, Ramon|||0000-0003-3427-1581
[EN] This paper studies the suitability of System-on-Chip (SoC) devices to perform Embedded Real-Time Simulators (eRTS) of electrical systems. These new devices combine powerful ARM processors, a Field-Programmable Gate Array (FPGA) and other peripherals which make them very convenient for controlling, monitoring and emulating a complete electrical system. There are two main categories of elements with their own respective characteristics and constraints: electromechanical/electromagnetic systems, and switching elements. Accordingly, the proposed investigation will focus on a Doubly-Fed Induction Generator (DFIG) on one hand, and on a Modular Multi-level Converter (MMC) on the other hand. In addition to Real-Time (RT) simulation results, SoC time/resources evaluations will be presented for different implementation strategies: full-software, full-hardware based on High-Level Synthesis (HLS) tools, and using 64/32-bit floating- and fixed-point formats. The validity of the MMC implementation will be tested experimentally., The authors would like to thank Mr Miguel Albero and Mr Raul Morillas for their help on building up the test bench to obtain the experimental results. Also thank the support of the Spanish Ministry of Economy and EU FEDER Funds under grants DPI2014-53245-R and DPI2017-84503-R.
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publicación Artículo científico (JournalArticle)

Wind power plant integration in voltage source converter HVdc grids with voltage droop control

  • Añó Villalba, Salvador Conrado|||0000-0002-8435-5225
  • Blasco-Gimenez, Ramon|||0000-0003-3427-1581
  • Bernal-Perez, Soledad|||0000-0002-5431-9792
  • Belenguer Balaguer, E.
[EN] This paper introduces the use of a diode-based HVdc rectifier for the integration of a large off-shore wind power plant into an existing HVdc voltage source converter-based grid. The proposed control system allows for the wind power plant to energize the complete HVdc grid, in order to contribute to service restoration in the case of a black-out. The system exhibits good response to wind power plant black-start operation, rectifier breaker trip and reclosure, and short-circuit ride through at the on-shore ac-grid. The technical feasibility of the proposed topology has been validated by means of detailed PSCAD simulations using frequency dependent parameters for cable modeling. (C) 2017 International Association for Mathematics and Computers in Simulation (IMACS). Published by Elsevier B.V. All rights reserved., The authors would like to thank the support of the Spanish Ministry of Economy and European Union FEDER Funds under grant DPI2014-53245-R.
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publicación Artículo científico (JournalArticle)

Sizing and Short-Circuit Capability of a Transformerless HVDC DC-DC Converter

  • Vidal-Albalate, Ricardo
  • Soto-Sánchez, Diego
  • Belenguer, Enrique
  • Peña, Rubén
  • Blasco-Gimenez, Ramon|||0000-0003-3427-1581
[EN] This work aims at optimizing the converter design of the double-T MMC DC-DC converter in terms of transmitted power per submodule and also in terms of transmitted power per silicon area, while, at the same time, providing the capability to block dc faults. Firstly, the converter operation is described and the optimal values of the inner ac and dc voltages that minimize device power rating are derived. Next, the submodule topology is analyzed and a thorough study on the converter capability for blocking fault currents is carried out, showing that the converter is able to isolate dc faults both at the input and at the output of the converter. Finally, the previous analytical study is verified by means of detailed PSCAD simulations., This work was supported by Spanish Ministry of Economy and EU FEDER Funds under Grants DPI2014-53245-R and DPI2017-84503-R. This work was supported by the EU through the Comunitat Valenciana 2014-2020 European Regional Development Fund (FEDER) Operating Program under Grant IDIFEDER/2018/036. This work was supported by the Fondecyt project 1201616 and CONICYT/FONDAP/15110019 is kindly acknowledged.
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publicación Contribución de congreso (ConferenceOutput)

Model aggregation of large wind farms for dynamic studies

  • Martínez-Turégano, Jaime|||0000-0002-3483-8253
  • Añó Villalba, Salvador Conrado|||0000-0002-8435-5225
  • Bernal-Perez, Soledad|||0000-0002-5431-9792
  • Blasco-Gimenez, Ramon|||0000-0003-3427-1581
  • Chaqués-Herráiz, G.
[EN] A large number of nodes is required for the detailed simulation of large off-shore wind farms. Therefore, the corresponding electromagnetic transient simulations require large simulation times. This paper compares a detailed model of an off-shore wind farm with three clusters of 50 wind turbines each one (i.e. a total of 150 wind turbines), with a simplified model consisting of three aggregated wind farms. The paper includes the aggregation criteria so equal power flows and voltages are obtained at the wind farms points of common coupling. The control is carried out using a centralized PI controller to control total active power, and a distributed droop control for active and reactive power control of each wind turbine. The proposed aggregation method leads to significant savings on computational times, with the aggregated models being more than three hundred and fifty times faster than the detailed ones. The results have been validated by means of detailed PSCAD/EMTDC simulations.v, The authors would like to thank the support of the Spanish Ministry of Economy and EU FEDER funds under grant DPI2014-53245-R. The support of CONICYT/FONDAP/15110019 and Fondecyt 1151325 is also kindly acknowledged. This project has received funding from the European Union's Horizon 2020 research and innovation program under grant agreement No. 691714.
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publicación Artículo científico (JournalArticle)

Efficient model for modular multi-level converter simulation

  • Vidal-Albalate, R.
  • Belenguer, E.
  • Beltrán, H.
  • Blasco-Gimenez, Ramon|||0000-0003-3427-1581
Detailed models of modular multi-level converters (MMCs) are cumbersome for electromagnetic transient simulation programs because of their high number of components which involve large simulation times. In this work, the modeling of an MMC is addressed with the objective of reducing the simulation time. First, the MMC structure is presented, including the modulation technique, the voltage balancing algorithm and the circulating current control used to validate the model. Next, an efficient simplified model is proposed. This is formed by just one variable voltage source, one variable capacitor and one variable resistor per arm, regardless of the number of submodules. This simplified model allows the simulation time to be reduced while keeping the dynamics of the MMC. The comparison through several PSCAD simulations with a detailed 5-level MMC model proves its validity during both steady-state and transient conditions (ac and dc short-circuits)., The authors acknowledge the financial support of the Spanish Ministry of Economy and EU FEDER Funds under Grant DPI2014-53245-R and the Universitat Jaume I under Grants P1.1B2013-51 and E-2014-24.