RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publicación Artículo científico (JournalArticle)

Design and assessment of a concentrating solar thermal system for industrial process heat with a copper slag packed-bed thermal energy storage

  • David-Hernandez, Marco Antonio
  • Cazorla-Marín, Antonio|||0000-0003-3314-0395
  • Calderon-Vásquez, Ignacio
  • Battisti, Felipe G.
  • Cardemil, José M.
[EN] Decarbonising the industrial sector is a key part of climate change mitigation targets, and Solar Heat for Industrial Process (SHIP) is a promising technology to achieve this. However, one of the drawbacks of SHIP systems is that they rely on an intermittent energy source. Therefore, sensible energy storage has emerged as a potential solution. In addition, solid byproducts have been proposed as a low-cost but effective material for thermal energy storage (TES). This work presents a SHIP system model coupled with a copper slag-packed-bed TES (PBTES) model using air as heat transfer fluid. The TES has been implemented to preheat the makeup water of the tank where steam is generated. A system design was carried out using a parametric analysis to find a solar field size and a corresponding TES volume. The resulting system was simulated, and the operating variables were analysed in detail. The results show that it is possible to generate 20% more energy due to the storage system. Additionally, a techno-economic analysis indicates that the SHIP with PBTES system results in a payback period of 14 years and a savings of CO2 emissions of 30 t CO2., This work was partially supported by the Research and Development Aid Program (PAID-01-20) of the Universitat Politecnica de Valencia for receiving the Research Fellowship FPI-UPV.2020, as well as the "Programa de Movilidad para estudiantes de doctorado" of the Universitat Politecnica de Valencia. This publication has also been partially supported by the project "DECARBONIZACION DE EDIFICIOS E INDUS-TRIAS CON SISTEMAS HI BRIDOS DE BOMBA DE CALOR", founded by the Spanish "Ministerio de Ciencia e Innovacion (MICIN) " with code number PID2020-115665RB-I00, as well as the R & D project Solar-Steam4IND (TED2021-130614 A -I00) , funded by MICIN/AEI/10.130 39/501100011033 and by the European Union NextGeneration EU/PRTR 2021 call. F. G. Battisti acknowledges the funding from ANID/CONICYT through FONDECYT Postdoctorado 2022 #3220792. J. M. Cardemil and F. G. Battisti acknowledge the financial support from project ANID/FONDAP/1523A0006 "Solar Energy Research Center (SERC) Chile".
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publicación Artículo científico (JournalArticle)

Selection of relevant features to detect and diagnose single and multiple simultaneous soft faults in air-source heat pumps

  • Llopis-Mengual, Belén|||0000-0003-0238-4231
  • Navarro-Peris, Emilio|||0000-0002-0608-2129
[EN] Soft faults in air-source heat pump systems can cause various issues, such as decreased performance, increased energy consumption, and long-term damage. This paper presents a comprehensive modeling approach of air-source heat pumps that considers individual and simultaneous soft faults validated against empirical experiments from the literature, a perspective limited in previous research. The methodology is based on the simulation of fault-free and faulty system performance utilizing heat pump modeling software. The results are a selection of variables and their trends to select the appropriate features to detect and diagnose single and double soft faults. The model also computes the impacts of these combined faults on COP, revealing significant reductions. Specifically, combinations of overcharge with condenser fouling and undercharge with compressor valve leakages induce COP reductions ranging from 17% to 38%, depending on operating conditions. The model can be used to develop faulty heat pump data, which can be adapted to other system typologies and conditions and used as input for data-driven Fault Detection and Diagnosis (FDD) methodologies., We gratefully acknowledge the financial support provided by the project "Decarbonizacion de edificios e industrias con sistemas hibridos de bomba de calor", funded by "Ministerio de Ciencia e Innovacion of Spain", with code number: PID2020-115665RB-I00. Belen Llopis-Mengual acknowledges the Ministry of Universities of Spain through the "Formacion de Profesorado Universitario"programme ref. FPU 19/04012.
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publicación Artículo científico (JournalArticle)

Modeling the performance of electronic expansion valves in heat pumps under soft faults

  • Llopis-Mengual, Belén|||0000-0003-0238-4231
  • Navarro-Peris, Emilio|||0000-0002-0608-2129
[EN] Heat pumps can have soft faults that cause them to keep operating but not as efficiently as they should. Detecting them is essential for proper maintenance. Nowadays, heat pumps usually include as expansion device electronic expansion valves (EEV), which generally control the superheat (SH) at the outlet of the evaporator. When soft faults occur, such as an undercharge or liquid line restrictions, the EEV opens to continue controlling the SH but becomes fully open at some point. Therefore, its behavior becomes a fixed orifice, and it can no longer continue to control. This study models the performance of the EEV for different conditions in heat pumps under soft faults, and it is validated with an experimental campaign in which the EEV opening is measured at different operating conditions and refrigerant charge levels. The evolution of the main system variables affected by the imposed fault levels of undercharge, overcharge, and liquid line restrictions are also analyzed., The authors wish to express their gratitude to Timo Methler and the Fraunhofer-Institut für Solare Energiesysteme ISE for the experimental campaign data gained during the publicly funded project 03EN4001A and used for this study. It is also acknowledged the Spanish Ministerio de Ciencia e Innovación , for their support with the project: PID2020-115665RB-I00 Decarbonización de edificios e industrias con sistemas híbridos de bomba de calor . B. Llopis-Mengual extends the acknowledgment to the Spanish Ministerio de Universidades for their support through the Formación de Profesorado Universitario program ref. FPU19/04012.
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publicación Artículo científico (JournalArticle)

Development of map-based models for the performance characterization in a new prototype of Dual Source Heat Pump

  • Marchante-Avellaneda, Javier|||0000-0001-5680-5033
  • Navarro-Peris, Emilio|||0000-0002-0608-2129
  • Song, Yang
[EN] This paper presents the development of accurate map-based models for characterizing a new Dual Source Heat Pump prototype. This unit includes three braze plate heat exchangers and a round tube fin heat exchanger, allowing the unit to select different operating modes such as heat pump, chiller, and domestic hot water production using as source the ground or air. Therefore, due to the hybrid typology of this unit and the possibility of reversing the cycle, this work covers the main heat pump and refrigeration equipment technologies currently available on the market (air source and ground source units). The modeling strategy selected has been to provide several polynomial expressions to predict the performance of these units, i.e., compressor energy consumption and condenser and evaporator capacities. This approach allows obtaining accurate, compact, and easy-to-implement models for developing dynamic models of more complex systems where this type of unit ¿ the heat pump ¿ is an integrated part of the system. Currently, a clear example of this modeling strategy can be found in characterizing one of the main components installed in these machines, the compressor. The AHRI-540 standard specifies a polynomial model as a function of evaporating and condensing temperatures. In this sense, for the characterization of heat pumps, the polynomials developed depend only on the unit¿s external variables, so they can be useful in many scenarios, obtaining direct feedback on the heat pump performance when developing a dynamic model to optimize system control strategies or to develop techno-economic studies. In this case, the hybrid typology of this unit makes it particularly relevant to optimize the control to manage the type of source to be used (air or ground), allowing the development of a more efficient and sustainable technology by selecting the most adequate source in terms of performance. This study focuses on obtaining the polynomial expressions that minimize the number of terms while simultaneously minimizing prediction error. By carefully selecting the most significant terms and suitable transformations in the characterized variables, the goal is to prevent overfitting, minimize potential extrapolation or interpolation errors and obtain polynomial expressions that can be fitted with small experimental samples. For this purpose, a detailed model implemented in a commercial software for heat pump characterization has been used, with which a large number of simulation results were generated. These simulation results include a fine meshing working map of the unit that allowed us to analyze the relationships between the characterized and external variables., The present work has been supported by the European Community Horizon 2020 Program for European Research and Technological Development (2014-2020) inside the framework of the project 656889 - GEOTeCH (Geothermal Technology for Economic Cooling and Heating) , by the project "DESCARBONIZACI & Oacute;N DE EDIFICIOS E INDUSTRIAS CONSISTEMAS H & Iacute;BRIDOS DE BOMBA DE CALOR", funded by the "Ministerio de Ciencia e Innovacion", MCIN, Spain, with code number: PID2020-115665RB-I00 and by the "Ministerio de Educacion, Cultura y Derporte", MECD, Spain, inside the program "Formacion de Profesorado Universitario (FPU15/03476) ". Many thanks as well to the late Dr. Jose Miguel Corberan, without whom this work would never have been possible. Sadly, Dr. Jose Miguel Corberan passed away in July of 2022. I wish to give my wholehearted support to Jose Miguel's family. I hope we did you proud.
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publicación Artículo científico (JournalArticle)

A novel methodology for map-based model fitting: A case study with a Dual Source Heat Pump experimental dataset

  • Marchante-Avellaneda, Javier|||0000-0001-5680-5033
  • Navarro-Peris, Emilio|||0000-0002-0608-2129
  • Barceló Ruescas, Francisco|||0000-0002-0577-2662
  • Song, Yang
[EN] This paper presents a new methodology to adjust map-based models to experimental data and reports the main results of a comprehensive experimental campaign of a Dual Source Heat Pump (DSHP) prototype. The prototype tested incorporates variable speed components (compressor, circulation pumps, and fan). The novelty of this prototype lies in its ability to select two possible heat sources: air or ground. Thus, it can operate as a geothermal or aerothermal heat pump, as well as a chiller, thanks to the additional capacity to reverse the cycle. Thanks to this hybrid approach, several advantages can be obtained compared to conventional equipment, such as higher efficiency, the requirement of smaller borehole heat exchangers, or the absence of defrost cycles. In a prior study, polynomial models were developed to accurately characterize the DSHP¿s performance (i.e., condenser and evaporator capacities and electrical energy consumption). These models were obtained considering the external variables to the unit as independent variables to facilitate their applicability using variables commonly measured in real installations. Due to the complexity of heat pump performance, which in current equipment can be influenced by up to 5 or 6 independent variables, the search for suitable polynomial models required the availability of a complete working map including more than 3000 working points. Thus, this previous work developed these models based only on simulation results. In this sense, this paper concludes the development of these models by focusing on two critical issues concerning empirical model development. The first aspect involves determining the minimum number and location of testing points needed to define the experimental sample for the model adjustment. The reported experimental data were obtained by analyzing the most suitable experimental design methodology to create the experimental matrices in each operating mode of the DSHP. The second aspect focuses on the final adjustment of models using experimental data. A novel fitting approach for empirical models is introduced in the last part of this study. The developed methodology enables the integration of simulation and experimental results for the final fitting of empirical models through a two-step adjustment. The first step involves analyzing and defining polynomial functionals from the complete working maps generated by simulation. Subsequently, in a second step, the polynomial models are refitted to a suitable experimental sample using the methodology presented in this work. The latter allows for the increase of the accuracy of the models and the minimization of experimental costs. This novel approach ensures a robust characterization of systems with many independent variables using a minimum amount of experimental data. Significant benefits can be obtained from its application, such as the reduction of experimental cost and an increase in the model¿s accuracy through an effective combination of both experimental and simulated information. Furthermore, it can be considered of general applicability to other engineering problems where the characterization of physical systems influenced by a high number of independent variables is required., The present work has been supported by the European Community Horizon 2020 Program for European Research and Technological Development (2014 2020) inside the framework of the project 656889 GEOTeCH (Geothermal Technology for Economic Cooling and Heating), by the project DESCARBONIZACIÓN DE EDIFICIOS E INDUSTRIAS CON SISTEMAS HÍBRIDOS DE BOMBA DE CALOR , funded by the Ministerio de Ciencia e Innovación , MCIN, Spain, with code number: PID2020-115665RB-I00 and by the postdoctoral fellowship funded by Universitat Politècnica de València inside the program Ayudas para Contratos de acceso de personal investigador doctor (PAID-10-23) . Many thanks as well to the late Dr. José Miguel Corberán, without whom this work would never have been possible. Sadly, Dr. José Miguel Corberán passed away in July of 2022. I wish to give my wholehearted support to José Miguel s family. I hope we did you proud.
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publicación Artículo científico (JournalArticle)

Enhanced monitoring and dynamics analysis of a concentrated solar thermal experimental plant for steam production

  • David-Hernandez, Marco Antonio
  • Cazorla-Marín, Antonio|||0000-0003-3314-0395
  • Gonzálvez-Maciá, José|||0000-0001-9422-7756
  • Payá-Herrero, Jorge|||0000-0003-2663-3191
  • Frasquet, Miguel
[EN] Solar heat for industrial processes (SHIP) is an increasingly interest option as a key strategy to decarbonise the industrial sector. Linear Fresnel Collectors are a promising technology due to their cost-effectiveness and efficiency. As part of the SOLPINVAP project, an experimental facility was constructed to prove the use of modular Linear Fresnel collectors for steam production in industrial processes. SHIP plants commonly use standard industrial sensors, which can result in high uncertainty when measuring absorbed and produced heat. This can be problematic when selling energy to customers through an energy purchase agreement. To address this issue, an uncertainty analysis was conducted in the experimental plant, and more precise instrumentation was added to the installation. This reduced the uncertainty in the absorbed energy in the solar field from 12% to 3% and obtaining an uncertainty of 3% in the generated energy. Additionally, the operation of the plant was studied through experimental tests conducted during the summer of 2022, and the system dynamics were analysed during the period of peak heat absorption., The authors gratefully acknowledge the company Solatom CSP, for the information and operational data from the SHIP facility, and for the technical support, specially to Juan Martinez and Carlo Terruzzi. This work was partially supported by the Research and Development Aid Program (PAID-01-20) of the Universitat Politecnica de Valencia for receiving the Research Fellowship FPI-UPV-2020. This publication hasbeen carried out in the framework of the project "DECARBONIZACION DE EDIFICIOS E INDUSTRIAS CON SISTEMAS HIBRIDOS DE BOMBA DE CALOR", founded by the Spanish "Ministerio de Ciencia e Innovacion (MICIN) " with code number PID2020-115665RB-I00. The project was also partially funded by the R&D project SolarSteam4IND (TED2021-130614A-I00) , funded by MICIN/AEI/10.13039/501100011033/and by the European Union NextGeneration EU/PRTR 2021 call.
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publicación Artículo científico (JournalArticle)

Modelling of a linear Fresnel solar thermal collector system for industrial processes and validation with on-site operational measurements

  • David-Hernandez, Marco Antonio
  • Cazorla-Marín, Antonio|||0000-0003-3314-0395
  • Gonzálvez-Maciá, José|||0000-0001-9422-7756
  • Payá-Herrero, Jorge|||0000-0003-2663-3191
[EN] The industry sector consumes one-third of the world's energy demand, where 70 % is used for heat-intensive processes. To meet this heat demand, fossil fuel-based technologies are typically employed, resulting in high carbon emissions. To decarbonise the industry sector, concentrating solar thermal technologies such as Fresnel collectors have been studied to demonstrate their techno-economic viability. This paper presents a new modular quasi-dynamic model that has been validated using measurements from two experimental campaigns conducted in an existing solar field facility. The model predicts the system's dynamic behaviour accurately, including the pressure evolution inside the tank with an error below 0.1 bar and the solar field temperatures with an error of around 0.5 K. Additionally, the difference between the daily measured and simulated generated energy is below 4.5 % on the analysed days. The model was also used to simulate the annual performance, resulting in a specific energy generation of 1604.5 MJ/m2 and a thermal efficiency of 27.8 %. Furthermore, a techno-economic analysis is conducted, incorporating a 20-year system lifetime, which yielded a payback period of 10 years and potential savings in CO2 emissions of 17.8 tCO2 per year., The company SOLATOM is acknowledged for all the information data of the SHIP plant. This work was partially supported by the Research and Development Aid Program (PAID-01-20) of the Universitat Politecnica de Valencia for receiving the Research Fellowship FPI-UPV.2020. This publication has been carried out in the framework of the project "DECARBONIZACION DE EDIFICIOS E INDUSTRIAS CON SISTEMAS HIBRIDOS DE BOMBA DE CALOR", founded by the Spanish "Ministerio de Ciencia e Innovacion (MICIN)" with code number PID2020-115665RB-I00. The project was also partially founded by the R & D project SolarSteam4IND (TED2021-130614A-I00), funded by MICIN/AEI/10.13039/501100011033 and by the European Union NextGeneration EU/PRTR 2021 call. Funding for open access charge: CRUE-Universitat Politecnica de Valencia.
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publicación Artículo científico (JournalArticle)

A critical analysis of the AHRI polynomials for scroll compressor characterization

  • Marchante-Avellaneda, Javier|||0000-0001-5680-5033
  • Navarro-Peris, Emilio|||0000-0002-0608-2129
  • Corberán, José M.
  • SHRESTHA
[EN] This paper presents the analysis of the energy consumption and mass flow rate of scroll-type compressors. The study has included the data of several AHRI reports (especially AHRI 11 and AHRI 21) and data from other sources. A total of 7 different scroll compressors of different sizes have been considered in the study, some of them tested with various refrigerants (R134a, R32, R410A, R404a¿). For all the studied compressors and refrigerants, the compressor energy consumption and mass flow rate values have been analyzed. The main objective is to better understand the dependence of these variables on the operating conditions and the refrigerant used. The analyzed data include tests following different superheat control, i.e., constant superheat or constant return temperature, so the effect of the inlet temperature on these variables is also discussed. As the main novelty of this study, the analysis of the response surfaces has allowed the authors to evaluate the most suitable correlation to use, including an analysis of the necessary experimental tests and where to place them to increase the model's accuracy. It was found that using the condensing and evaporating pressure terms is more universal than the classical temperature domain. In scroll compressors, AHRI polynomials overfits the compressor performance introducing significant deviations in the interpolation and extrapolation capabilities if the experimental data are not properly selected. Finally, it was found that lower degree polynomials are more suitable for this kind of compressor and has also the advantage of requiring fewer experimental point measurements to characterize the compressor with the corresponding cost-savings., The present work has been supported by the project "DECARBONIZACION DE EDIFICIOS E INDUSTRIAS CON SISTEMAS HIBRIDOS DE BOMBA DE CALOR", funded by "Ministerio de Ciencia e Innovacion", MCIN, Spain, with code number: PID2020-115665RB-I00 and by the Ministerio de Educacion, Cultura y Derporte inside the program "Formacion de Profesorado Universitario (FPU15/03476)".
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publicación Artículo científico (JournalArticle)

Refrigerant charge distribution in brine-to-water heat pump using R290 as refrigerant, Distribution de la charge en frigorigène dans une pompe à chaleur saumure/eau utilisant le R290 comme frigorigène

  • Sánchez-Moreno-Giner, Luis
  • Methler, Timo
  • Barceló Ruescas, Francisco|||0000-0002-0577-2662
  • Gonzálvez-Maciá, José|||0000-0001-9422-7756
[EN] This paper presents experimental results from a brine-to-water heat pump used for space heating at low tem-perature, with a low refrigerant charge of R290 (propane). Performance and refrigerant distribution were ana-lysed in every test condition studied. Performance results show a declared heating capacity of 9.5 kW, obtaining a specific capacity (C-c) of 48.7 kW rmkg(-1) and a seasonal coefficient of performance of 4.01. In terms of refrigerant distribution, at the nominal point, 41.5% of the refrigerant is located in the compressor, mainly dissolved in the oil, and the rest is separated almost evenly in both heat exchangers, 23.9% in the condenser and 27.8% in the evaporator; having the lines and accessories (pneumatic-ball valves) the remaining 6.8%. Due to this fact, reducing oil solubility by heating the crankcase or increasing the superheat (SH) has a positive impact on the refrigerant charge reduction, but it also affects the coefficient of performance., The authors would like to acknowledge the Spanish "MINISTERIO DE CIENCIA E INNOVACION", through the project ref- PID2020-115665RB-I00 "Descarbonizacion de Edificios e Industrias con sistemas híbridos de bomba de Calor" for the given support. The authors also would like to acknowledge the "Conselleria dInnovacio, Universitats, Ciencia i Societat Digital de la Generalitat Valenciana" through the Project "AICO/2021/078" for the given support. Also, the study presented in this paper received funding from the German Federal Ministry of Economic Affairs and Climate Action (BMWK) under the grant agreement numbers FKZ 03EN4001A (LC150) . Lastly, the experimental campaign was performed during an international stay financed by "Ayudas para movilidad de estudiantes de Doctorado de la Universitat Politecnca de Valencia" during the doctoral thesis financed by (PAID -01-17)
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publicación Artículo científico (JournalArticle)

Effects of simultaneous soft faults in a reversible and variable-speed air-to-water heat pump

  • Llopis-Mengual, Belén|||0000-0003-0238-4231
  • Navarro-Peris, Emilio|||0000-0002-0608-2129
[EN] The widespread adoption of air-to-water heat pumps is driven by their high heating efficiency, with some systems offering reversibility for cooling applications. Despite their benefits, these systems are susceptible to soft faults such as undercharge, overcharge, and outdoor unit airflow restrictions (condenser fouling in cooling mode or evaporator fouling in heating mode). Detecting and addressing these faults before they escalate into hard faults is critical. While previous experimental studies have focused on residential heat pumps with imposed faults, most were conducted on air-to-air systems, primarily in cooling mode and with fixed-speed compressors. This study addresses the gap by investigating a reversible air-to-water heat pump employing R290 and a variable-speed compressor. The experimental work consists of imposing faults of undercharge, overcharge, condenser and evaporator fouling, individually and in combination. The investigation analysis considers the system¿s behavior under these faults in cooling and heating modes and how the control strategy (subcooling or superheat) and a compressor suction accumulator affect it. In cooling mode, the combination of 85% undercharge and 50% condenser fouling worsens the EER up to 39% if the superheat is controlled and up to 10% if the subcooling is controlled. In heating mode with subcooling control, 85% undercharge combined with a 50% evaporator fouling can worsen the COP by 32%. However, there are cases where those same fault levels only impact the COP by 4% due to the charge requirements of the condition and that the excess charge is stored in the compressor suction accumulator. As compressor speed can significantly affect the refrigerant charge requirements of the system, this work shows its potential for fault detection, particularly for undercharge. These findings can provide a basis for developing Fault Detection and Diagnosis methodologies for reversible air-to-water heat pumps with variable-speed compressors., We gratefully acknowledge the financial support provided by the project "Decarbonizacion de edificios e industrias con sistemas hibri-dos de bomba de calor", funded by "Ministerio de Ciencia e Innovacion"of Spain, with project code: PID2020-115665RB-I00. Belen Llopis-Mengual extends her appreciation to the Ministry of Universities of Spain through the "Formacion de Profesorado Universit ario" programme ref. FPU 19/04012.
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publicación Artículo científico (JournalArticle)

Fault detection and diagnosis algorithm for multiple simultaneous faults in residential air-conditioning systems: Development, validation study and critical analysis

  • Llopis-Mengual, Belén|||0000-0003-0238-4231
  • Navarro-Peris, Emilio|||0000-0002-0608-2129
  • Yuill, David
[EN] Detecting and diagnosing faults in residential air conditioning (AC) systems is crucial for preventing critical failures and ensuring efficient operation. Some of these soft faults are refrigerant undercharge (UC), overcharge (OC), inadequate evaporator airflow (EA), or liquid line restrictions (LL). Data-driven methodologies have proven effective in achieving reliable detection but require a large amount of data. This paper proposes utilizing a model based on vapor compression cycles capable of simulating a wide range of indoor/outdoor operating conditions and faults imposed individually and several co-occurring (multiple combinations) for a residential AC unit. This simulated dataset is used to train a Support Vector Machine (SVM) classification algorithm to distinguish between fault, non-fault, and multiple fault states. The SVM uses features obtained from a small number of sensors, making this methodology adequate for residential AC units that typically have limited instrumentation. The proposed method is applied to the same simulated unit, which is experimentally tested in the laboratory with imposed faults, resulting in a balanced accuracy of 82% and a weighted F1-score of 84%. These results demonstrate the feasibility of training a fault detection and diagnosis algorithm with simulation data without requiring an extensive experimental campaign., The authors gratefully acknowledge the financial support provided by the project "Decarbonizacion de edificios e industrias con sistemas hibridos de bomba de calor", funded by "Ministerio de Ciencia e Innovacion" of Spain, with project code: PID2020-115665RB-I00. Belen Llopis-Mengual extends her appreciation to the Ministry of Universities of Spain through the "Formacion de Profesorado Universitario" programme ref. FPU19/04012 and the funding to conduct a research stay EST23/00752.
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publicación Artículo científico (JournalArticle)

Comparison and selection of experimental designs for the characterization of scroll and reciprocating compressors: Adjustment of polynomial models with compact experimental samples

  • Marchante-Avellaneda, Javier|||0000-0001-5680-5033
  • Navarro-Peris, Emilio|||0000-0002-0608-2129
  • Shrestha, Som S.
[EN] The use of refrigeration equipment and heat pumps is a widely used solution by manufacturers in the industry. Selecting components for this equipment and simulating their behavior require a thorough understanding and effective characterization of the compressor. In this sense, the standard AHRI-540 is the most used one to characterize compressor performance (Wc and mref) considering polynomial models of 10 coefficients. Unfortunately, this standard does not offer information about where to perform the required experimental measurements for the model adjustment. Drawing on these precedents, this paper investigates various Design of Experiments methodologies to identify the most efficient approaches for characterizing both scroll and reciprocating compressors with minimal experimental points. The study aims to develop a straightforward methodology for optimal point selection, ensuring precise compressor characterization while minimizing experimental costs. For this purpose, two datasets from two Copeland scroll compressors ¿ ZP21K5E-PFV and ZS21KAE-PFV ¿ with massive test campaigns have been employed. Both compressors were subjected to a substantial number of experimental points (1097 and 866) across different suction conditions (SH=11K, SH=22K, Tsuc=18°C) and different refrigerants (R134a, R32, R410A, R404a, ¿). In a first step, this study presents the design of experimental matrices for characterizing efficiently the energy consumption and mass flow rate in scroll compressors. Additionally, the energy consumption is also characterized from the specific energy consumption (Wesp), i.e., the energy consumption divided by the mass flow rate. Considering that the specific energy consumption obtains equal dependencies between scroll and reciprocating compressors, the matrices performed for the specific energy consumption are also suitable for the characterization of reciprocating compressors, also allowing to obtain compact experimental matrices with a low number of points., The present work has been supported by the project "DESCAR- BONIZACION DE EDIFICIOS E INDUSTRIAS CON SISTEMAS HIBRIDOS DE BOMBA DE CALOR", funded by the "Ministerio de Ciencia e Innovacion", MCIN, Spain, with code number: PID2020-115665RB-I00 and by the "Ministerio de Educacion, Cultura y Deporte", MECD, Spain, inside the program "Formacion de Profesorado Universitario (FPU15/03476)". This research used resources at the Building Technologies Research and Integration Center, a DOE Office of Science User Facility operated by the Oak Ridge National Laboratory of USA. Many thanks as well to the late Dr. Jose Miguel Corberan, without whom this work would never have been possible. Sadly, Dr. Jose Miguel Corberan passed away in July of 2022. I wish to give my wholehearted support to Jose Miguel's family. I hope we did you proud.
RiuNet. Repositorio Institucional de la Universitat Politécnica de Valéncia
Publicación Artículo científico (JournalArticle)

Analysis of map-based models for reciprocating compressors and optimum selection of rating points, Analyse de modèles basés sur des abaques pour les compresseurs alternatifs et sélection optimale des points d évaluation

  • Marchante-Avellaneda, Javier|||0000-0001-5680-5033
  • Navarro-Peris, Emilio|||0000-0002-0608-2129
  • Corberan, J.M.
  • Shrestha, Som S.
[EN] The present work includes an in-depth performance analysis in fixed-speed reciprocating compressors. The industry standard for compressor characterization is the AHRI-540, which uses a 10-term and third-degree polynomial to characterize mass flow rate and energy consumption. However, the suitability of such a high-degree polynomial is unclear, and the potential for overfitting and extrapolation errors cannot be ignored. This work analyzes the response surfaces of mass flow rate and energy consumption in reciprocating compressors to determine if more concise models with lower degrees are more suitable. For that purpose, a massive experimental dataset with multiple compressors using different refrigerant and suction conditions was analyzed to obtain overall conclusions in the compressor field. The results of the present work showed that mass flow rate modeling requires lower-degree polynomials. However, the energy consumption characterization is more complex, and the model reported in the standard may be justified. Additionally, it was found that, if the specific energy consumption is selected as the modeling variable, it is possible to use a compact polynomial expression, which can also be extended to scroll compressors and also has the advantage of reducing the experimental data necessary for the model fit. Finally, by selecting the mass flow rate and the specific energy consumption as response variables, this work also explores other critical issues related to the experimental points¿ location and minimum sample sizes required in order to minimize the experimental costs and increase the model accuracy., The present work has been supported by the project "DESCARBONIZACION DE EDIFICIOS E INDUSTRIAS CON SISTEMAS HIBRIDOS DE BOMBA DE CALOR", funded by the "Ministerio de Ciencia e Innovacion", MCIN, Spain, with code number: PID2020-115665RB-I00 and by the "Ministerio de Educacion, Cultura y Deporte", MECD, Spain, inside the program "Formacion de Profesorado Universitario (FPU15/03476)". This research used resources at the Building Technologies Research and Integration Center, a DOE Office of Science User Facility operated by the Oak Ridge National Laboratory of USA.