Pasar al contenido principal

INTEGRACION EN SISTEMAS DE CALEFACCION Y REFRIGERACION DE DISTRITO DEL ALMACENAMIENTO DE ENERGIA TERMICA (TES) PARA AUMENTAR LA FRACCION SOLAR Y EL USO DE FUENTES RENOVABLES

ENE2014-57262-R

•
Nombre agencia financiadora Ministerio de Economía y Competitividad
Acrónimo agencia financiadora MINECO
Programa Programa Estatal de I+D+i Orientado a los Retos de la Sociedad
Convocatoria Proyectos I+D+i Retos de Investigación
Año convocatoria 2014
Plan Estatal 2013-2016 Plan Estatal de Investigación Científica y Técnica y de Innovación
Unidad de gestión Secretaría de Estado de Educación, Formación Profesional y Universidades
Centro beneficiario UNIVERSIDAD DE ZARAGOZA
Identificador persistente http://dx.doi.org/10.13039/501100003329

Resultados relacionados

Resultados totales (Incluyendo duplicados): 13
Encontrada(s) 1 página(s)

Zaguán. Repositorio Digital de la Universidad de Zaragoza
Publicación Artículo científico (JournalArticle)

An approach to the integrated design of PCM-air heat exchangers based on numerical simulation: a solar cooling case study

  • Dolado Bielsa, Pablo
  • Lázaro Fernández, Ana
  • Delgado Gracia, Mónica
  • Peñalosa García, Conchita
  • Mazo Olarte, Javier
  • Marín Herrero, José María
  • Zalba Nonay, Belén
A novel technique of design of experiments applied to numerical simulations is proposed in this paper as a methodology for the sizing and design of thermal storage equipment integrated in any specific application. The technique is carried out through the response surfaces in order to limit the number of simulation runs required to achieve an appropriate solution. Thus, there are significant savings on the time spent on the design as well as a potential cost saving on the experimentation if similarity relationships between the prototype and the model are met. The technique is applied here to a previously developed and validated numerical model that simulates the thermal behavior of a phase change material-air heat exchanger. The incorporation of the thermal energy storage unit is analyzed in the case of a solar cooling application, improving the system coefficient of performance. The economic viability is mainly conditioned by the price of the macroencapsulated phase change material.
Zaguán. Repositorio Digital de la Universidad de Zaragoza
Publicación Artículo científico (JournalArticle)

IEA SHC Task 42 / ECES Annex 29 - Working Group B: Applications of Compact Thermal Energy Storage

  • Van Helden, W
  • Yamaha, M
  • Rathgeber, C
  • Hauer, A
  • Huaylla, F
  • Le Pierrès, N
  • Stutz, B
  • Mette, B
  • Dolado, P
  • Lazaro, A
  • Mazo, J
  • Dannemand, M
  • Furbo, S
  • Campos-Celador, A
  • , Diarce, G
  • Cuypers, R
  • König-Haagen, A
  • Höhlein, S
  • Brüggemann, D
  • Fumey, B
  • Weber, R
  • Köll, R
  • Wagner, W
  • Daguenet-Frick, X
  • Gantenbein, P
  • Kuznik, F
The IEA joint Task 42 / Annex 29 is aimed at developing compact thermal energy storage materials and systems. In Working Group B, experts are working on the development of compact thermal energy storage applications, in the areas cooling, domestic heating and hot water and industry. The majority of application projects were in the field of room heating and domestic hot water. In this article, an overview is given of a large number of applications. The storage technologies used in the applications are latent heat storage, open and closed solid sorption, liquid sorption and salt hydrates and composites thereof. On a broad front, a lot of progress was made in the development of components and systems, providing knowledge and experience regarding the design, numerical modeling, building, testing and economical assessing of components and storage systems. Most important findings are that the interaction of storage materials with the materials of components can be deciding for the technical feasibility, that a number of components, like reactor, heat exchangers and evaporators are less understood than initially thought and need more development, that the inclusion of storage materials in systems generate new challenges like the occurrence of non-condensable gases and thermo-mechanical effects and that standardized and simplified system approaches are needed.
Zaguán. Repositorio Digital de la Universidad de Zaragoza
Publicación Artículo científico (JournalArticle)

IEA SHC Task 42 / ECES Annex 29 - A Simple Tool for the Economic Evaluation of Thermal Energy Storages

  • Rathgeber, C
  • Hiebler, S
  • Lävemann, E
  • Dolado, P
  • Lazaro, A
  • Gasia, J
  • De Gracia, A
  • Miró, L
  • Cabeza, L.F
  • König-Haagen, A
  • Brüggemann, D
  • Campos-Celador, Á
  • Franquet, E
  • Fumey, B
  • Dannemand, M
  • Badenhop, T
  • Diriken, J.j
  • Nielsen, J.E.
  • Hauer, A
Within the framework of IEA SHC Task 42 / ECES Annex 29, a simple tool for the economic evaluation of thermal energy storages has been developed and tested on various existing storages. On that account, the storage capacity costs (costs per installed storage capacity) of thermal energy storages have been evaluated via a Top-down and a Bottom-up approach. The Top-down approach follows the assumption that the costs of energy supplied by the storage should not exceed the costs of energy from the market. The maximum acceptable storage capacity costs depend on the interest rate assigned to the capital costs, the intended payback period of the user class (e.g. industry or building), the reference energy costs, and the annual number of storage cycles. The Bottom-up approach focuses on the realised storage capacity costs of existing storages. The economic evaluation via Top-down and Bottom-up approach is a valuable tool to make a rough estimate of the economic viability of an energy storage for a specific application. An important finding is that the annual number of storage cycles has the largest influence on the cost effectiveness. At present and with respect to the investigated storages, seasonal heat storage is only economical via large sensible hot water storages. Contrary, if the annual number of storage cycles is sufficiently high, all thermal energy storage technologies can become competitive.
Zaguán. Repositorio Digital de la Universidad de Zaragoza
Publicación Artículo científico (JournalArticle)

A theoretical study on the accuracy of the T-history method for enthalpy-temperature curve measurement: Analysis of the influence of thermal gradients inside T-history samples

  • Mazo, J.
  • Delgado, M.
  • Lázaro, A.
  • Dolado, P.
  • Peñalosa, C.
  • Marín, J.M.
  • Zalba, B.
The present work analyses the effect of radial thermal gradients inside T-history samples on the enthalpy temperature curve measurement. A conduction heat transfer model has been utilized for this purpose. Some expressions have been obtained that relate the main dimensionless numbers of the experiments with the deviations in specific heat capacity, phase change enthalpy and phase change temperature estimations. Although these relations can only be strictly applied to solid materials (e.g. measurements of shape stabilized phase change materials), they can provide some useful and conservative bounds for the deviations of the T-history method. Biot numbers emerge as the most relevant dimensionless parameters in the accuracy of the specific heat capacity and phase change enthalpy estimation whereas this model predicts a negligible influence of the temperature levels used for the experiments or the Stefan number.
Zaguán. Repositorio Digital de la Universidad de Zaragoza
Publicación Artículo científico (JournalArticle)

Porosity and density measurements of sodium acetate trihydrate for thermal energy storage

  • Dannemand, Mark
  • Delgado, Monica
  • Lazaro, Ana
  • Penalosa, Conchita
  • Gundlach, Carsten
  • Trinderup, Camilla
  • Johansen, Jakob Berg
  • Moser, Christoph
  • Schranzhofer, Hermann
  • Furbo, Simon
Sodium acetate trihydrate (SAT) can be used as phase change material in latent heat storage with or without utilizing supercooling. The change of density from liquid to solid state leads to formation of cavities inside the bulk SAT during solidification. Samples of SAT which had solidified from supercooled state at ambient temperature and samples which had solidified with a minimal degree supercooled were investigated. The temperature dependent densities of liquid and the two types of solid SAT were measured with a density meter and a thermomechanical analyzer. The cavities formed inside samples of solid SAT, which had solidified after a high or minimal degree of supercooling, were investigated by X-ray scanning and computer tomography. The apparent density of solid SAT depended on whether it solidified from a supercooled state or not. A sample which solidified from a supercooled liquid contained 15% cavities and had a density of 1.26¿g/cm3 at 25¿°C. SAT which had solidified with minimal supercooling contained 9% cavities and had a density of 1.34¿g/cm3 at 25¿°C. The apparent densities of the solid SAT samples were significant lower than the value of solid SAT reported in literature of 1.45¿g/cm3. The density of liquid and supercooled SAT with extra water was also determined at different temperatures.
Zaguán. Repositorio Digital de la Universidad de Zaragoza
Publicación Artículo científico (JournalArticle)

Thermoeconomic cost allocation in simple trigeneration systems including thermal energy storage

  • Pina, E.A.
  • Lozano, M.A.
  • Serra, L.M.
The present paper tackles the issue of allocating economic costs in trigeneration systems including thermal energy storage (TES) for buildings of the residential-commercial sector. As energy systems become more and more complex (multiple resources, products and technologies; joint production; TES) the issue of the appropriate way to allocate the cost of the resources consumed arises. This is important because the way in which allocation is made directly affects the prices of the products obtained and, thus, the consumers' behavior. Thermoeconomics has been used to explain the cost formation process in complex energy systems. In this paper, two issues in thermoeconomics that have not been deeply studied are addressed: (i) the joint production of energy services in dynamic energy systems; and (ii) the incorporation of TES. A thermoeconomic analysis of a simple trigeneration system including TES was performed and the hourly unit costs of the internal flows and final products were obtained for a day of the year. The cost allocation proposal considered that the cogenerated products must share the benefits of the joint production. Regarding the TES, the interconnection between charging and discharging periods was explored, allowing the discharged energy flow to be traced back to its production period.
Zaguán. Repositorio Digital de la Universidad de Zaragoza
Publicación Artículo científico (JournalArticle)

Allocation of economic costs in trigeneration systems at variable load conditions including renewable energy sources and thermal energy storage

  • Pina, E.A.
  • Lozano, M.A.
  • Serra, L.M.
As energy systems become more and more complex, the issue of the appropriate way to allocate the cost of the resources consumed increases because the way in which allocation is made directly affects the prices of the products obtained and, thus, the consumers’ behavior. Thermoeconomics has been used to explain the cost formation process in complex energy systems. The thermoeconomic analysis of a trigeneration system including renewable energy sources (RES) and thermal energy storage (TES) was developed to determine the energy, capital, and total unit costs of the internal flows and final products. This work addresses issues not yet deeply studied in thermoeconomics, namely the joint production of energy services in dynamic energy systems and the incorporation of TES, RES (photovoltaic panels) and a component with different products for each operation mode (heat pump producing heat in heating mode and cooling in cooling mode). The interconnection between charging and discharging periods through the TES units was explored, allowing the discharged flow to be traced back to its production period. The trigeneration system resulted more profitable than the reference system, with total cost savings of 9942 €/yr, which was translated into the lower annual total unit costs of the final products.
Zaguán. Repositorio Digital de la Universidad de Zaragoza
Publicación Artículo científico (JournalArticle)

Optimal operation and marginal costs in simple trigeneration systems including thermal energy storage

  • Pina, Eduardo A.
  • Lozano, Miguel A.
  • Serra, Luis M.
The development of high-efficiency energy systems is a pressing issue nowadays, motivated by economic, environmental, and social aspects. Trigeneration systems allow for the rational use of energy by means of appropriate energy integration and provide greater operational flexibility, which is particularly interesting for buildings, often characterized by variable electricity, heating, and cooling demands. The benefits of trigeneration systems can be enhanced by the incorporation of thermal energy storage (TES), which decouples production and consumption. This paper analyses the operation of a simple trigeneration system including TES. The optimal operation is obtained by a linear programming model that minimizes the total variable cost. A thermoeconomic analysis based on marginal cost assessment of the internal flows and final products of the system is carried out, allowing to explain the optimal operation of the system and the role of the TES in achieving the optimal solution. The analysis unravels the marginal cost formation process, presenting a clear route from the final products obtained to the resources consumed. This information can aid the design of new plants, the retrofit of existing ones, and the operational management to achieve the minimum operational cost.
Zaguán. Repositorio Digital de la Universidad de Zaragoza
Publicación Artículo científico (JournalArticle)

Evaluation of the suitability of different calorimetric methods to determine the enthalpy-temperature curve of granular PCM composites

  • Mazo, Javier
  • Delgado, Mónica
  • Peñalosa, Conchita
  • Dolado, Pablo
  • Miranda, Inés
  • Lázaro, Ana
  • Marín, José María
  • Zalba, Belén
The present research has analyzed the complementarity of different measuring methodologies when characterizing the phase changing behaviour of a granular PCM composite (GPCC) through a comparison of their results. Specifically, the enthalpy variation of the GR31 product manufactured by Rubitherm has been measured by using: (1) An energy balance calculation of an air stream flowing through a GPCC packed bed; (2) Differential Scanning Calorimetry; (3) the T-history method. The main purpose of this study was to evaluate the suitability of these methods for the enthalpy-temperature curve determination of GPCC. The energy balance setup gave an accurate measurement of the enthalpy variation within a sufficiently high temperature interval. Obtaining a representative sample was not a problem using this method, in contrast to the DSC which requires a greater number of tests to obtain an average value representative of the packed bed. However, the energy balance method does not enable the direct determination of the enthalpy-temperature curve. The T-history methodology allows the enthalpy to be determined based on temperature while the representativeness problem of the DSC is avoided due to the higher sample volume. Nevertheless, the sample must be altered, crushed and subsequently compacted to reduce the effects of the thermal resistances provoked by the void spaces being filled by air. This comparison has shown that there is no single valid methodology for characterizing the phase changing behaviour of PCM granules.
Zaguán. Repositorio Digital de la Universidad de Zaragoza
Publicación Artículo científico (JournalArticle)

Experimental analysis of a coiled stirred tank containing a low cost PCM emulsion as a thermal energy storage system

  • Delgado, M.
  • Lázaro, A.
  • Mazo, J.
  • Peñalosa, C.
  • Marín, J. M.
  • Zalba, B.
This article presents the results of heat transfer coefficient and volumetric energy density measurements in an agitated tank containing a low-cost phase change material emulsion, heated by water flowing in a coil. For the stirring a three-stage impeller is placed in the central axis of a 46 l commercial tank. By measuring the temperature dependency on time and solving the transient enthalpy balance, the heat transfer coefficient between the helical coil and the agitated phase change material emulsion is determined, based on the impeller Reynolds number. The thermal energy storage efficiency has also been analysed. This phase change material emulsion shows a phase change temperature range between 30 and 50 °C. Its solid content is about 60% with an average size of 1 µm. The results have shown that the overall heat transfer coefficient is around 3.5–5.5 times higher when a stirring rate of 290–600 rpm is used. Furthermore, even at the lowest stirring rate, the thermal energy storage efficiency improves from 76-77%–100%, without detriment to the energy consumption of the stirrer.
Zaguán. Repositorio Digital de la Universidad de Zaragoza
Publicación Artículo científico (JournalArticle)

Air infiltrations and energy demand for residential low energy buildings in warm climates

  • Guillén-Lambea, Silvia
  • Rodríguez-Soria, Beatriz
  • Marín, José M.
European building legislation is establishing increasingly stricter requirements to reduce the energy demand of buildings as a measure to decrease energy use and associated carbon emissions. In order to comply with the new standards, the most impactful parameters are subject to important revisions. Airtightness is revealed as an impacting parameter on air conditioning energy demand for nearly Zero Energy Buildings (nZEB). Currently the Passivhaus standard, taken as a constructive reference for nZEB in Europe, establishes 0.6 ACH as the maximum infiltration at 50 Pa for all new buildings irrespective of the climate zone. Nevertheless, the influence of infiltrations on the energy demand is lower in warm climates. This study estimates the potential heating and cooling energy demand for different levels of infiltration rates in southern Europe. For this purpose, a dwelling equipped with a mechanical ventilation system with a heat exchanger has been simulated in TRNSYS. The calculations have been performed in different cities with different levels of infiltrations. This research provides the information required to set airtightness parameters in residential buildings in southern Europe to satisfy the new requirements for nZEB.
Zaguán. Repositorio Digital de la Universidad de Zaragoza
Publicación Artículo científico (JournalArticle)

Experimental analysis of a low cost phase change material emulsion for its use as thermal storage system

  • Delgado, M.
  • Lázaro, A.
  • Mazo, J.
  • Peñalosa, C.
  • Dolado, P.
  • Zalba, B.
A 46 l commercial tank with a helical coil heat exchanger and containing a low cost phase change material emulsion has been experimentally analyzed as a thermal energy storage system in terms of volumetric energy density and heat transfer rate, for its subsequent comparison with other thermal energy storage systems. This phase change material emulsion shows a phase change temperature range between 30 and 50°C, its solids content is about 60% with an average particle size of 1 µm. The low cost phase change material emulsion shows a thermal storage capacity by mass 50% higher than water and an increase in viscosity up to 2-5 orders of magnitude. The results have shown that the global heat transfer coefficient of the phase change material emulsion tank is around 2-6 times higher than for conventional latent systems previously analyzed in literature, although 5 times lower than if it contains water. The phase change material emulsion tank presents an energy density 34% higher than the water tank, which makes it a promising solution. Measures to improve its performance are also studied in this work.
Zaguán. Repositorio Digital de la Universidad de Zaragoza
Publicación Artículo científico (JournalArticle)

Intercomparative tests on viscosity measurements of phase change materials

  • Delgado, M.
  • Lázaro, A.
  • Biedenbach, M.
  • Gamisch, S.
  • Gschwander, S.
  • Höhlein, S.
  • König-Haagen, A.
  • Brüggemann, D.
Phase change materials (PCM) are capable of storing thermal energy within a small temperature range due to their high latent heat. When designing a thermal energy storage (TES) system with PCMs, besides the phase change enthalpy, thermal conductivity and density, viscosity based on temperature must be characterized to take into account natural convection. Taking advantage of the facilities of the different research groups working within an international network, a set of intercomparative tests were executed to determine the viscosity based on the temperature of two PCMs: octadecane and the commercial paraffin RT70 HC. Three laboratories have participated, which have used three different rheology equipments: two controlled stress rheometers, AR-G2 from TA Instruments and MCR 502 from Anton Paar and a translational rheometer, IMETER. The intercomparative tests were executed based on a starting methodology approach defined previously by some of the authors. The highest deviations were observed when temperature-controlled geometries or temperature hoods were not used at elevated test temperatures due to the temperature gradients within the sample, as consequence of the heat losses due to the room temperature. Consequently, special attention must be focused on the temperature control, since a uniform temperature throughout the sample should be guaranteed.